8.1 Alarm Displays
8.1.3 INDEXER Alarm Displays and Troubleshooting
8-38
8.1.3
INDEXER Alarm Displays and Troubleshooting
INDEXER alarms and corrections for them are given in the following table.
Error
Number
Alarm
Number
Alarm Name
Meaning
Corrective Action
Servo-
motor
Stop
Method
Alarm
Reset
E19A
A.EF9
Program Table
Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The program table
stored in flash mem-
ory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
program table is
being saved or ini-
tialized.)
•
Initialize the pro-
gram table. (Fn063)
•
If the problem is not
solved, correct the
program table.
Gr.1
Available
*1
E1AA
A.EF9
Program Table
Version
Unmatched
(Detected only
when control
power supply is
ON.)
The combination of
the firmware version
and the program
table version is
wrong.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1BA
A.EF9
Program Out-
of-range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
program table is not
within the allowed
setting range.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1CA
A.EF9
ZONE Table
Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The ZONE table
stored in flash mem-
ory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
ZONE table is being
saved or initialized.)
•
Initialize the ZONE
table. (Fn064)
•
If the problem is not
solved, correct the
ZONE table.
Gr.1
Available
*2
E1DA
A.EF9
ZONE Table
Version
Unmatched
(Detected only
when control
power supply is
turned ON.)
The combination of
the firmware version
and the ZONE table
version is wrong.
•
Change the firm-
ware version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
E1EA
A.EF9
ZONE Table
Out-of-range
Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
ZONE table is not
within the allowed
setting range.
•
Change the firm-
ware version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
Continued on next page.