8.6 Autotuning without Host Reference
8.6.3 Operating Procedure
8
T
uning
8-25
Preparations
Always check the following before you execute autotuning without a host reference.
•
The main circuit power supply must be ON.
•
There must be no overtravel.
•
The servo must be OFF.
•
The control method must not be set to torque control.
•
The gain selection switch must be set to manual gain selection (Pn139 = n.
0).
•
The first gains must be selected.
•
The test without a motor function must be disabled (Pn00C = n.
0).
•
There must be no alarms or warnings.
•
The parameters must not be write prohibited.
•
The tuning-less function must be disabled (Pn170 = n.
0).
•
If you execute autotuning without a host reference during speed control, set the mode to 1.
8.6.3
Operating Procedure
Use the following procedure to perform autotuning without a host reference.
1.
Confirm that the moment of inertia ratio (Pn103) is set correctly.
2.
Click the
Servo Drive
Button in the workspace of the Main Window of the Sig-
maWin+.
3.
Select
Tuning
in the Menu Dialog Box.
The Tuning Dialog Box will be displayed.
Click the
Cancel
Button to cancel tuning.
•
If you start autotuning without a host reference while the SERVOPACK is in speed control
for mode 2 or 3, the SERVOPACK will change to position control automatically to perform
autotuning without a host reference. The SERVOPACK will return to speed control after
autotuning has been completed.
Information
CAUTION
If you specify not estimating the moment of inertia, set the moment of inertia ratio (Pn103)
correctly. If the setting greatly differs from the actual moment of inertia ratio, normal control
of the machine may not be possible, and vibration may result.
If you are using the SERVOPACK for phase control, set the mode selection to 1. If 2 or 3 is
selected for the mode, correct phase control may not be possible.