Yaskawa Solectria Solar
DOCR-071069
Page
23
of
24
4.4 Replacement Fuses
Fuses in the AC Combiner
Only replace the fuses in the ACC1500-500 AC Combiner with appropriately-rated
fuses. The specification for the fuses in the AC Combiner are in Table 4.3 below.
Fuse
Rating
Part Number
Inverter Output Circuit
200A, 600VAC
Time-Delay
Class J
Mersen AJT200N
AC Output Circuit
600A, 600VAC
Time-Delay
Class J
Mersen AJT600N
AC Combiner Fuse Specifications