4.2 System OFF Procedure
To turn off the PVS-500, the following turn-off sequence is recommended to avoid
unnecessary wear out of the components:
Turn OFF all three of the XGI-1500 red on/off switches on the right side of an inverter.
Press the DPS 500 emergency OFF (EPO) button on the front panel of the converter.
Turn the disconnect handle on the AC combiner to the OFF position
Turn OFF all 5 DC disconnect switches on the front of the DC Recombiner
Turn OFF the DC disconnect switches on the DCP 500 converter.
4.3 System ON Procedure
To turn on the PVS-500, use the following turn-on sequence:
Close all PV source circuit fuse holders in the combiner boxes and close the cover.
Turn the DC disconnect switches on the DCP 500 converter to the ON position.
At each combiner, turn the DC disconnect to the ON position.
Turn ON all 5 DC disconnect switches on the front of the DC Recombiner
Turn the disconnect handle on the AC combiner to the ON position
Release the DPS 500 emergency off (EPO) button on the front panel of the converter.
Turn ON all three of the XGI-1500 red on/off switches on the right side of an inverter.