A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Single-Phase Derating
P1000 drives are compatible for use with both three-phase and single-phase input power supplies. The drive output to the
motor is always three-phase, regardless of number of input phases.
Output capacity to the motor is derated when using single-phase input power and the drive firmware includes protection for
single-phase input applications. This protection is enabled by default. Disabling this protection for single-phase input
applications can void warranty and result in premature failure.
Selection of larger models always results in greater output capacity to the motor when supplying the drive with three-phase
input power. However, the selection of larger models does not always yield greater output capacity when using the drive with
single-phase input power.
Several factors affect the amount of derated drive output capacity when single-phase input power is supplied to the drive, such
as:
• single-phase input voltage level
• motor voltage rating
• amount of input impedance.
The tables in this section assist in model selection by considering factors that affect the amount of derating in single-phase
input power applications.
n
Single-Phase Input Sizing (Continuous Full Power)
The Output Capacity Motor FLA listed in the tables allows for a 120% overload for 60 seconds. Contact Yaskawa if assistance
is needed in selecting drive models for heavy duty/single-phase applications with higher overload requirements.
Note:
Adding more impedance than is specified will degrade performance.
Service Factor
When using a service factor greater than 1.15, multiply the nominal power (HP) by the service factor (SF), then select a drive
with a higher power rating than the product of that equation.
Example:
1.5 HP x 1.3 SF = 1.95 SF HP
The user should select a 2 HP or larger drive.
Table A.13 240 V Single-Phase Input (-5% to +10%), 230 V Three-Phase Motor
Drive Model
Without Additional Impedance
With Additional Impedance
(use either DC type or AC type)
Yaskawa Reactor Part Number
Motor Power
(HP)
Drive Input
Current (A)
Motor Power
(HP)
Drive Input
Current (A)
DC Type
AC Type
2A0004
1/3
4.3
URX000043
URX000303
1/2
4.1
2A0006
3/4
7.7
URX000043
URX000303
3/4
5.7
2A0008
1
9.5
05P00620-0113
URX000307
1
7.2
2A0010
1
9.5
05P00620-0113
URX000311
1
7.8
2A0012
1.5
13.7
URX000048
URX000316
2
13
2A0018
2
19
05P00620-0120
URX000319
3
19
2A0021
2
19
05P00620-0120
URX000323
3
19
2A0030
3
27
05P00620-0120
URX000323
3
19
2A0040
3
27
05P00620-0124
URX000323
5
30
2A0056
5
43
URX000059
URX000326
7.5
42
2A0069
7.5
62
URX000063
URX000332
10
56
2A0081
10
79
URX000072
URX000338
15
84
A.4 Drive Derating Data
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
407
A
Specifications
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......