Table 5.25 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
6
200
1.3 2.5
50
12
V
oltage (V)
Frequency (Hz)
0
6
200
1.5 3
60
12
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.26 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
5
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
5
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.27 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
7
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
200
1.3 2.5
50
20
V
oltage (V)
Frequency (Hz)
0
7
200
1.5 3
60
15
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
20
V
oltage (V)
Frequency (Hz)
Table 5.28 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
6
12
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
6.9
230
1.5 3
60
13.8
V
oltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
Refer to V/f Pattern on page 195
pattern.
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
60.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
575.0 V
E1-06
Base Frequency
0.0 to [E1-04]
60.0 Hz
E1-07
Middle Output Frequency
0.0 to [E1-04]
3.0 Hz
E1-08
Middle Output Frequency Voltage
15.0 V
E1-09
Minimum Output Frequency
0.0 to [E1-04]
1.5 Hz
E1-10
Minimum Output Frequency Voltage
9.0 V
E1-11
Middle Output Frequency 2
0.0 to [E1-04]
E1-12
Middle Output Frequency Voltage 2
0.0 V
5.5 E: Motor Parameters
194
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......