No.
(Addr.
Hex)
Name
Description
Values
Page
o1-15
(3107)
Frequency Reference and
Frequency Related Monitor
Custom Units 3
Sets the third character of the customer-specified unit display when o1-03 is
set to 3 and o1-09 is set to 24.
Default: 41
Range: 30 to 7A
–
<1> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.
u
o2: Digital Operator Keypad Functions
No.
(Addr.
Hex)
Name
Description
Values
Page
o2-01
(505)
LO/RE Key Function
Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Range: 0, 1
–
o2-02
(506)
STOP Key Function
Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Range: 0, 1
–
o2-03
(507)
User Parameter Default
Value
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Default: 0
Range: 0 to 2
–
o2-04
(508)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board. Default:
Determined by
drive capacity
–
o2-05
(509)
Frequency Reference
Setting Method Selection
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using
the up and down arrow keys only.
Default: 0
Range: 0, 1
–
o2-06
(50A)
Operation Selection when
Digital Operator is
Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: An oPr fault is triggered and the motor coasts to stop.
Default: 1
Range: 0, 1
–
o2-07
(527)
Motor Direction at Power
Up when Using Operator
This parameter requires assigning drive operation to the digital operator.
0: Forward
1: Reverse
Default: 0
Range: 0, 1
–
o2-20
(81E)
Operator RUN Save at
Power Loss
When running during a power loss, the Run command is issued via the digital
operator and the Run state is saved to the EEPROM.
When power is restored, the Run command is automatically applied if the
LOCAL/REMOTE or FREF conditions have not changed in the drive.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
u
o3: Copy Function
No.
(Addr.
Hex)
Name
Description
Values
Page
o3-01
(515)
Copy Function Selection
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved
on the operator.
Default: 0
Range: 0 to 3
–
o3-02
(516)
Copy Allowed Selection
0: Read operation prohibited
1: Read operation allowed
Default: 0
Range: 0, 1
–
u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name
Description
Values
Page
o4-01
(50B)
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h. Default: 0
Min.: 0
Max.: 9999
–
o4-02
(50C)
Cumulative Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Default: 0
Range: 0, 1
–
B.9 o: Operator-Related Settings
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
219
B
Parameter List