A.2 Parameter Table
320
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
E4-04
Motor 2 Motor
Poles
Sets the number of poles of motor 2. This
value is automatically set during Auto-Tuning.
2 to 48 4 poles A A
−
324
E4-05
Motor 2
Line-to-Line
Resistance
Sets the phase-to-phase resistance of motor 2
in ohms. Automatically during Auto-Tuning.
0.000 to
65.000
A A
−
325
E4-06
Motor 2
Leakage
Inductance
Sets the voltage drop due to motor leakage
inductance as a percentage of rated voltage of
motor 2. Automatically set during
Auto-Tuning.
0.0 to
40.0
A A
−
326
E4-07
Motor 2 Motor
Iron-Core
Saturation
Coefficient 1
Set to the motor iron saturation coefficient at
50% of magnetic flux. Automatically set
during Rotational Auto-Tuning.
0.00 to
0.50
0.50
−
A
−
343
E4-08
Motor 2 Motor
Iron-Core
Saturation
Coefficient 2
Set to the motor iron saturation coefficient at
75% of magnetic flux. This value is
automatically set during Rotational
Auto-Tuning.
Setting
for
E4-07 to
0.75
0.75
−
A
−
344
E4-09
Motor 2
Mechanical
Loss
Sets the motor mechanical loss as a percentage
of motor rated power (kW) capacity.
Adjust in the following circumstances:
When there is a large amount of torque loss
due to motor bearing friction.
When there is a large amount of torque loss.
0.00 to
10.0
0.0
−
A
−
33F
E4-10
Motor 2 Iron
Loss
Sets the motor iron loss in watts.
0 to
65535
Α − −
340
E4-11
Motor 2 Rated
Capacity
Sets the motor rated capacity in kW.
Automatically set during Auto-Tuning.
0.00 to
650.00
A A
−
327
E4-12
Motor 2
Iron-Core
Saturation
Coefficient 3
Set to the motor iron saturation coefficient at
130% of magnetic flux. Automatically set
during Rotational Auto-Tuning.
1.30 to
5.00
1.30
−
A
−
342
E4-14
Motor 2 Slip
Compensation
Gain
Sets the slip compensation gain for motor 2.
The function is the same as C3-01 for motor 1.
Refer to the C3-01 description.
0.0 to 2.5
0.0
A A
−
341
E4-15
Torque
Compensation
Gain - Motor 2
Sets the torque compensation gain for motor 2.
The function is the same as C4-01 for motor 1.
Refer to the C4-01 description.
1.00 to
2.50
1.00
A A
−
341
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
PM
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...