A.2 Parameter Table
304
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
b5-14
PID Feedback Loss
Detection Time
Sets the PID feedback loss detection delay time
in terms of seconds.
0.0 to
25.5
1.0 s A A A
1B2
b5-15
PID Sleep Function
Start Level
Sets the sleep function start frequency.
Note:
Also enabled when PID is not active.
0.0 to
400.0
0.0
Hz
A A A
1B3
b5-16
PID Sleep Delay Time Sets the sleep function delay time.
0.0 to
25.5
0.0 s A A A
1B4
b5-17
PID Accel/Decel Time Applies an accel/decel time to the PID setpoint.
0 to
255
0 s A A A
1B5
b5-18
PID Setpoint Selection
Selects b5-19 as PID setpoint value.
0: Disabled
1: Enabled, b5-19 becomes PID target
0,1
0
A A A 1DC
b5-19
PID Setpoint Value
Sets the PID target value when b5-18 = 1.
0.00 to
100.00
0.00
%
A A A 1DD
b5-20
PID Setpoint Scaling
Sets the units for b5-19, and for parameter
monitors U5-01 (PID Feedback) and U5-04
(PID Setpoint).
0: 0.01Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must be set up)
3: User-set (set to b5-38 and b5-39)
0 to 3
1
A A A
1E2
b5-34
PID Output Lower
Limit
Sets the minimum output possible from the PID
controller.
-100.0 to
+100.0
0.00
%
A A A
19F
b5-35
PID Input Limit
Limits the PID control input (deviation signal).
Acts as a bipolar limit.
0 to
1000.0
1000.
0%
A A A
1A0
b5-36
PID Feedback High
Detection Level
Sets the PID feedback high detection level.
0 to 100
100
%
A A A
1A1
b5-37
PID Feedback High
Level Detection Time
Sets the PID feedback high level detection
delay time.
0.0 to
25.5
1.0 s A A A
1A2
b5-38
PID Setpoint / User
Display
Sets the display value of U5-01 and U5-04
when the maximum frequency is output.
Changeable only if b5-20 = 3.
0 to 60000: User-Set Display if b5-20=3
1 to
60000
A A A
1FE
b5-39
PID Setpoint Display
Digits
Sets the number of digits of U5-01 and U5-04.
Changeable only if b5-20 = 3.
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
0 to 3
A A A
1FF
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...