272
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
2.8 Message Examples
2.8
Message Examples
Below are some examples of command and response messages.
◆
Reading Drive MEMOBUS/Modbus Register Contents
Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can
be read out at a time.
The following table shows message examples when reading status signals, error details, data
link status, and frequency references from the slave 2 drive.
Command Message
Response Message (normal)
Response Message (fault)
Slave Address
02H
Slave Address
02H
Slave Address
02H
Function Code
03H
Function Code
03H
Function Code
83H
Starting
No.
Upper
00H
Data Quantity
08H
Error Code
03H
Lower
20H
1st storage
register
Upper
00H
CRC-16
Upper
F1H
Data
Quantity
Upper
00H
Lower
65H
Lower
31H
Lower
04H
Next
storage
register
Upper
00H
CRC-16
Upper
45H
Lower
00H
Lower
F0H
Next
storage
register
Upper
00H
Lower
00H
Next
storage
register
Upper
01H
Lower
F4H
CRC-16
Upper
AFH
Lower
82H
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...