1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
159
Pa
ra
m
et
er D
et
ai
ls
1
Figure 1.53
Figure 1.53 During Run Timechart
Setting 1: Zero Speed
Terminal closes whenever the output frequency falls below the minimum output frequency
set to E1-09.
Figure 1.54
Figure 1.54 Zero-Speed Timechart
Setting 2: Speed Agree 1 (fref / fout Agree 1)
Closes whenever the actual output frequency is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09
Closed
Output frequency is less than the minimum output frequency set to E1-09
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
OFF
Output frequency
or
motor speed
Zero Speed
ON
E1-09 (Max. Output Frequency)