A.1 MP3200 Installation and Usage Conditions
A.1.1 Environmental Conditions
A-2
A.1
MP3200 Installation and Usage Conditions
Install the MP3200 Controller in an environment with the following conditions.
A.1.1
Environmental Conditions
Control Panel Cooling Method
The components that are used in the MP3200 require the ambient operating temperature to be
between 0 and 55
°
C. Use one of the methods described below to ensure adequate cooling in
the control panel.
Control Panels with Natural Cooling
•
Do not mount the MP3200 at the top of the control panel, where the hot air that is generated
inside the panel collects.
•
Leave sufficient space above and below the MP3200, and maintain adequate distances from
other devices, cable ducts, and other objects to ensure suitable air circulation.
•
Do not mount the Machine Controller in any direction other than the specified direction.
•
Do not mount the Machine Controller on top of any device that generates a significant
amount of heat.
•
Do not subject the Machine Controller to direct sunlight.
Item
Specification
Ambient Operating Tempera-
ture
0 to 55
°
C
Ambient Storage Temperature
−
25 to 85
°
C
Ambient Operating Humidity
30% to 95% RH (with no condensation)
Ambient Storage Humidity
5% to 95% RH (with no condensation)
Pollution Degree
Conforms to JIS B 3502 Pollution Degree 2.
Corrosive Gases
There must be no combustible or corrosive gases.
Operating Altitude
2,000 m max.
•
If the ambient temperature exceeds 50
°
C, we recommend forced-air cooling.
•
The CPU-202 is force-cooled with a built-in fan.
Note