Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death
or serious injury. Ensure the areas surrounding the drive, motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
WARNING! When performing Rotational Auto-Tuning, always uncouple the motor from the mechanical system (remove ropes from
traction sheave). Performing Rotational Auto-Tuning with the mechanical system connected to the motor can cause hazardous
situations, injury to personnel, and damage to the equipment.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is applied on the load. Ensure the motor can freely spin
before beginning Auto-Tuning. Failure to comply could result in improper operation of the drive.
Enter the required information from the motor nameplate. Press
to proceed to the Auto-Tuning start display.
Note:
These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
u
Input Data for Motor Auto-Tuning: T1
The T1-
parameters are used to set the Auto-Tuning input data.
Note: 1.
Cycling drive power after setting the T1 parameters will reset these parameters to default values.
2.
For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete,
change E1-04, Maximum Output Frequency, to the desired value.
n
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
Refer to Types of Auto-Tuning on page 80
for details on the different types of
Auto-Tuning.
Setting 0: Rotational Auto-Tuning
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
n
T1-02: Motor Rated Power
Sets the motor rated power according to the motor nameplate value.
Step
Display/Result
1.
After entering the data listed on the motor nameplate, press
to confirm.
2.
Press
to activate Auto-Tuning. The drive begins by injecting current into the motor for about 1 min,
and then starts to rotate the motor.
3.
Auto-Tuning finishes in approximately one to two minutes if no errors occur.
No.
Name
Setting Range
Default
T1-01
Auto-Tuning Mode Selection
2 (V/f)
0 to 2 (OLV)
2 (V/f)
0 (OLV)
No.
Name
Setting Range
Default
T1-02
Motor Rated Power
0.00 to 650.00 kW
Determined by o2-04
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...