188
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
Code
Name
Causes
Possible Solutions
Unsatisfactory balance between voltage phases.
•
Examine the supply voltage for problems.
•
Make the drive input power stable.
•
If the supply voltage is good, examine the magnetic contactor
on the main circuit side for problems.
The main circuit capacitors have become
unserviceable.
•
Examine the capacitor maintenance time in monitor
U4-05
[CapacitorMaintenance]
.
•
If
U4-05
is more than 90%, replace the capacitor. Contact
Yaskawa or your nearest sales representative for more
information.
•
Examine the supply voltage for problems.
•
Re-energize the drive.
•
If the alarm stays, replace the circuit board or the drive. For
information about replacing the control board, contact
Yaskawa or your nearest sales representative.
Note:
•
The drive detects this error if the DC bus voltage changes irregularly without regeneration.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
Use
L8-05 [Input Phase Loss Protection Sel]
to enable and disable
PF
detection.
Code
Name
Causes
Possible Solutions
SToF
Safe Torque OFF Failure
One of the two terminals H1-HC and H2-HC
received the Safe Disable input signal.
The Safe Disable input signal is wired incorrectly.
•
Make sure that the Safe Disable signal is input from an
external source to terminals H1-HC or H2-HC.
•
When the Safe Disable function is not in use, connect
terminals H1-HC and H2-HC.
There is internal damage to one Safe Disable
channel.
Replace the board or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
Note:
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
Code
Name
Causes
Possible Solutions
TiM
Keypad Time Not Set
There is a battery in the keypad, but the date and
time are not set.
Set the date and time with the keypad.
Note:
•
Parameter
o4-24 [bAT Detection Selection]
enables and disables
TiM
detection.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
TrPC
IGBT Maintenance Time (90%)
The IGBT is at 90% of its expected performance
life.
Replace the IGBT or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
UL3
Undertorque Detection 1
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault
The parameters are incorrect for the load.
Adjust
L6-02 [Torque Detection Level 1]
and
L6-03 [Torque
Detection Time 1]
.
Note:
•
The drive detects this error if the drive output current is less than the level set in
L6-02
for longer than
L6-03
.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
Set the conditions that trigger the minor fault using
L6-01 [Torque Detection Selection 1]
.
Code
Name
Causes
Possible Solutions
UL4
Undertorque Detection 2
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault
The parameters are incorrect for the load.
Adjust
L6-05 [Torque Detection Level 2]
and
L6-06 [Torque
Detection Time 2]
.
Note:
•
The drive detects this error if the drive output current is less than the level set in
L6-05
for longer than
L6-06
.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
•
Set the conditions that trigger the minor fault using
L6-04 [Torque Detection Selection 2]
.
Code
Name
Causes
Possible Solutions
Uv
DC Bus Undervoltage
The drive input power voltage is changing too
much.
•
Use a better power supply voltage to align with the drive rated
voltage.
•
Make the drive input power stable.
•
If there is not a fault with the input power supply, examine the
magnetic contactor on the main circuit side for faults.
A phase loss occurred in the drive input power.
Correct errors with the wiring for main circuit drive input power.
There is loose wiring in the drive input power
terminals.
Examine for loose screws and tighten them as specified by the
tightening torque values in the manual.
There was a loss of power.
Use a better power supply.
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...