5.11 S: Elevator Parameters
■ S4-08: UPS Operation Speed Limit Selection
Determines how a speed limit should be applied to the Rescue Operation speed (d1-25) when operating from a UPS. The
drive calculates the appropriate speed limit based on the UPS capacity set in S4-07. This speed limit helps prevent
voltage saturation and motor stall during Rescue Operation.
No.
Parameter Name
Setting Range
Default
S4-08
U PS Operation Speed Limit Selection
0 to 2
2
0: Disabled
1: Enabled until Light Load Direction Search is complete
2: Enabled until stop
■ S4-12: DC Bus Voltage during Rescue Operation
Sets the DC bus voltage during Rescue Operation.
No.
Parameter Name
Setting Range
Default
S4-12
DC Bus Voltage during R escue Operation
0 to 800 V
0 V
■ S4-13: Rescue Operation Power Supply Deterioration Detection Level
Determines at which level o f backup power supply deterioration a PF5 fault is triggered. The following conditions will
trigger PF5:
• During Rescue Operation, DC bus voltage < [S4-12 x (S4-13 - 10%)]
• 100 ms after Rescue Operation has been triggered, the DC bus voltage does not rise above S4-12 x S4-13 before the
motor starts
No.
Parameter Name
Setting Range
Default
S4-13
R escue Operation Power Supply Deterioration Detection Level
10 to 100%
80%
■ S4-15: Speed Reference Selection at Rescue Operation
Note: Available in drive software PRG: 7016 and later.
Selects the speed reference used for Rescue Operation.
No.
Parameter Name
Setting Range
Default
S4-15
Speed Reference Selection for R escue Operation
0, 1
0
0: The setting of parameter d1-25 is used as speed reference fo r Rescue Operation
1: The speed selected by digital inputs is used as speed reference
♦ S5: Short Floor Operation
■ Short Floor Function
Short Floor automatically adjusts the speed in order to reduce the leveling time if leveling speed was activated before the
selected speed was reached. Short Floor is enabled setting S5-01 = 1. The drive calculates the distance to decelerate from
rated speed to the leveling speed, then controls the stop so that the stopping time is shortened. In
Figure 5.45
below, area
S indicates the distance for a stop from nominal speed.
Speed
d1-19 (nominal speed)
nominal speed
x
0.4
d1-26 (leveling speed)
0
t
F ig u r e 5 .4 5 S p e e d D u rin g N o rm a l O p e r a tio n
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
225
P
a
ra
m
e
te
r
D
e
ta
il
s
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...