5.8 L: Protection Functions
■ L1-02: Motor Overload Protection Time
Sets the detection time o f motor overheat due to overload. This setting rarely requires adjustment, but should correlate
with the motor overload tolerance protection time for performing a hot start.
No.
Name
Setting Range
Default
L1-02
Motor Overload Protection Time
0.1 to 5.0 minutes
1.0 minutes
Defaulted to operate with an allowance o f 150% overload operation for one minute in a hot start.
Figure 5.33
illustrates an example o f the electrothermal protection operation time using a general-purpose motor
operating at the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when
starting a stationary motor.
• Hot start: Motor protection operation time in response to an overload situation that occurred during sustained
operation at rated current.
F ig u r e 5 .3 3 M o to r P r o t e c ti o n O p e r a tio n T im e
■ L1-13: Continuous Electrothermal Operation Selection
Determines whether to hold the current value o f the electrothermal motor protection (L1-01) when the power supply is
interrupted.
No.
Name
Setting Range
Default
L1-13
Continuous Electrothermal Operation Selection
0 or 1
1
Setting 0: Disabled
Setting 1: Enabled
♦ L2: Undervoltage Detection
■ L2-05: Undervoltage Detection Level (Uv)
Determines the voltage at which a U v1 fault is triggered. This setting rarely needs to be changed.
No.
Name
Setting Range
Default
L2-05 <1>
Undervoltage Detection Level
150 to 210 Vdc
Determined by E1-01
<1> Values shown are specific to 200 V class drives; double the values for 400 V class drives.
Note: Install an AC reactor option on the input side o f the pow er supply when setting L2-05 below the default value to prevent damage
to drive circuitry.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
191
P
a
ra
m
e
te
r
D
e
ta
il
s
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...