12 Travel Direction Change Counter
86
YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
Note:
•
If o4-40 is active and you have not set a password, a
TCS alarm [TDCC Setup Alarm]
is present.
•
During maintenance, log the values for
U4-64 to U4-68
and
o4-41
occasionally.
If a drive brakes and cannot be powered on anymore, these values cannot be restored. In such a case, a person responsible for elevator
safety must decide if ropes need to be replaced or if values can be estimated.
◆
Counter Reset
To reset the Travel Direction Change Counter (TDCC) after you replaced ropes, enter the limit of bending
changes to
TDCC Pres Value [o4-42]
. The value entered is in thousands, e.g. when you enter
‘
1
’
it means 1000
direction changes are allowed.
When you entered the value, the monitors
Rem Dir Chg [U4-65, U4-66]
will be updated, and
04-42
will be reset
to
0
.
◆
Related Parameters and Monitors
■
Added Parameters
Parameter
Operator Display
Content
Value Range
Default Value
o4-40
TDCC Enable
Travel Direction Change Counter Enable
Enables the TDCC function:
0 : Disabled
1 : Enabled
0, 1
0
o4-41
TDCC Alarm Level
Travel Direction Change Counter Alarm Level
Sets the Trip Counter Alarm level. The value is set in units of 1 kilo
(1000).
0k - 10000k
50k
o4-42
TDCC Pres Value
Travel Direction Change Counter Preset Value
Sets the number of allowable direction changes after a rope change. The
unit is kilo (1k = 1000). The
direction counter [U4-66/U4-67]
is set to the
input value and the parameter is changed back to 0.
0k - 65535k
0k
o4-43
TDCC Pswd Set
Travel Direction Change Counter Password Setting
Sets the Travel Direction Change Counter password. The password needs
to be entered twice (identically). The active password locks parameters
o4-
40 to o4-43
from editing and starts the TDC counting process. The
password can only be set when
o4-40
is enabled. When the same password
is entered again, the parameters are unlocked again. The password is not
displayed. A coded value is shown:
0 : Password not set
1 : Password set
2 : Password set and entered (unlocked)
3 - FFFF : Password
Only values 3 to FFFFh are accepted as password.
A set password is not reset by A1-03 initialization (including EEPROM
initialization 9990).
0 - FFFF
0
■
Added Monitors
Parameter
(Hex.)
Operator Display
Content
Analog Output
Scaling
Range/Unit
U4-65
(830)
Rem Dir Chg L
Shows the lower three digits of actual TDCC value. It is reset to 0 after
1000 direction changes.
-
0 - 999
U4-66
(831)
Rem Dir Chg H
Shows the remaining upper digits of actual TDCC value.
-
0k - 65535k
U4-67
(832)
Total Dir Chg L
Shows the lower three digits of total TDCC value. It is reset to 0 after 1000
direction changes.
-
0 - 999
U4-68
(833)
Total Dir Chg H
Shows the remaining upper digits of total TDCC value (1 = 1000 = 1k).
The value saturates at 65535k.
-
0k - 65535k
U4-69
(834)
Total TDCC Pres
Shows the number of preset operations (includes reset to 0) of the TDCC.
The value saturates at 63. This is intended to uncover possible misuse.
-
0 - 63
U4-70
(835)
Last DirChg Pres
Shows the most recent value, input to
o4-42
for resetting the remaining
direction changes counter.
-
0 - 65535k
Содержание L1000A CIMR-LC F Series
Страница 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 97: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 97 15 Appendix EN...
Страница 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Страница 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Страница 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...