Содержание J1000 CIMR-JC series

Страница 1: ...rt Guide 3 ENGLISH J1000 Quick Start Guide ENGLISH 1 Safety Instructions and General Warnings 4 2 Mechanical Installation 9 3 Electrical Installation 11 4 Keypad Operation 16 5 Start Up 18 6 Parameter...

Страница 2: ...user Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the manual NO OTHER WARRANTY EXPRESS OR IMPLIED IS OFFERED Ya...

Страница 3: ...ndicators are off and measure the DC bus voltage level to confirm safe level Do not allow unqualified personnel to use equipment Failure to comply could result in death or serious injury Maintenance i...

Страница 4: ...metal or other noncombustible material Do not connect AC line power to output terminals U V and W Make sure that the power supply lines are connected to main circuit input terminals R L1 S L2 T L3 or...

Страница 5: ...ble for circuits capable of delivering not more than 100 000 RMS symmetrical Amperes 240 Vac maximum 200 V Class and 480 Vac maximum 400V Class Do not use unshielded cable for control wiring Failure t...

Страница 6: ...pliance when using this drive in combination with other equipment Do not install the drive to an area greater than pollution severity 2 UL standard Use UL listed copper wires rated at 75 C and closed...

Страница 7: ...itions Installation Area Indoors Ambient Temperature 10 C to 50 C When using an enclosure panel install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclo...

Страница 8: ...5 38 5 109 5 M4 1 0 BA0006 108 128 137 5 96 118 5 58 129 M4 1 7 BA0010 108 128 154 96 118 5 58 145 5 M4 1 8 2A0001 68 128 76 56 118 5 6 5 67 5 M4 0 6 2A0002 68 128 76 56 118 5 6 5 67 5 M4 0 6 2A0004...

Страница 9: ...ch Forward Stop Reverse Stop External Fault Fault Reset Multi speed 1 Multi function digital inputs default setting Link Thermal relay Braking resistor option J1000 Ground Multi function relay output...

Страница 10: ...2 5 M3 5 M3 5 M3 5 BA0006 FS23638 20 07 A6T40 2 5 M4 M4 M4 BA0010 FS23638 20 07 A6T40 4 M4 M4 M4 2A0001 FS23637 8 07 A6T10 2 5 M3 5 M3 5 M3 5 2A0002 FS23637 8 07 A6T10 2 5 M3 5 M3 5 M3 5 2A0004 FS2363...

Страница 11: ...r compliance with the EN61000 3 2 Refer to the instruction manual or contact your supplier for details EMC Standards Compliant Wiring of Single and Three Phase Units Main and Control Circuit Wiring Wi...

Страница 12: ...voltage output can cause large peak currents thus tripping the over current detection or damage the drive Ground Connection Take the following precautions when grounding the drive Never share the gro...

Страница 13: ...nt input SW3 Used to select sourcing PNP sinking NPN default mode for the digital inputs PNP requires external 24 Vdc power supply Type No Terminal Name Signal Function Signal Level Default Setting Mu...

Страница 14: ...power up Up Arrow Key Scrolls up to select parameter numbers setting values etc Down Arrow Key Scrolls down to select parameter numbers setting values etc STOP Key Stops the drive ENTER Key Selects mo...

Страница 15: ...utput Current Output Voltage Monitor Display Verify Menu Setup Mode Parameter Setting Mode DRV LED is on A Run command will start the motor The Monitor Displays are used to read out drive data like te...

Страница 16: ...necessary Final check the operation and verify the settings Drive is ready to run the application Intstall and wire the drive as explained Turn the power on Initialize the drive if necessary using pa...

Страница 17: ...n the REMOTE mode Mode Heavy Duty Ratings HD Normal Duty Rating ND C6 01 0 1 Application Applications with a constant torque like extruders conveyors and cranes High overload capability might be neede...

Страница 18: ...Select the input sig nal level in parameter H3 01 NOTICE If the input signal level of input A1 is switched between voltage and current make sure that DIP switch S1 is in the correct position and para...

Страница 19: ...he C2 parameters for softer accel decel start and end Test Run Perform the following steps to start up the machine after all parameter settings have been done 1 Run the motor without load and check if...

Страница 20: ...s the DC Injection Braking cur rent as a percentage of the drive rated current b2 03 DC Inj Braking Time DC Excitation Time at Start Sets the time of DC Injection Brak ing at start in units of 0 01 se...

Страница 21: ...ng current in Ampere E2 05 Motor Line to Line Resistance Sets the phase to phase motor resistance in ohms Digital Input Settings H1 01 to H1 05 DI S1 to S5 Function Selection Selects the function of t...

Страница 22: ...ent A U1 06 Output Voltage Reference Vac U1 07 DC Bus Voltage Vdc U1 10 Input Terminal Status Par Name Description 1 Digital input 1 terminal S1 enabled 1 Digital input 2 terminal S2 enabled 1 Digital...

Страница 23: ...on is assigned to one of the digital inputs and the input is off The drive does not accept Run commands ControlCircuit Fault There is a problem in the drive s control circuit Cannot Reset Fault reset...

Страница 24: ...eavy The drive capacity is too small Too much torque at low speed DC Overvoltage DC bus voltage rose too high The deceleration time is too short Stall prevention is disabled Braking chopper resistor b...

Страница 25: ...per values oPE03 A contradictory setting is assigned to multi func tion contact inputs H1 01 through to H1 05 The same function is assigned to two inputs this excludes External fault and Not used Inpu...

Страница 26: ...7 Troubleshooting 28 TOEP C710606 27 J1000 Quick Start Guide...

Страница 27: ...he revised manuals are given on the bottom of the back cover Date of Publication Rev No Section Revised Contents January 2008 First edition MANUAL NO TOEP C710606 27A Published in Japan January 2008 0...

Отзывы: