No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
b5-44
(0163)
PI Output 2 Monitor
Max Lower 4 Digits
PI Out2 MonMax L
Sets the lower 4 digits of the maximum monitor value.
Used with b5-43 to set maximum monitor value of U5-14 and
U5-15 at maximum frequency.
Note:
Used for U5-14 and U5-15 only.
Default: 0
Min.: 0
Max.: 99.99
–
b5-45
(0164)
PI Output 2 Monitor
Minimum
PI Out2 MonMin
Sets the minimum display value at zero speed.
This function is effective when b5-42 is set to 0 (Linear output
mode).
Note:
Used for U5-14 and U5-15 only.
Default: 0
Min.: 0
Max.: 999.9
–
b5-47
(017D)
Reverse Operation
Selection 2 by PID
Output
Output Rev Sel2
0: Zero limit when PID output is a negative value.
1: Reverse operation when PID output is a negative value
(Zero limit if the reverse operation is prohibited by b1-04).
Default: 1
Range: 0, 1
–
<1> Unit text is set by P1-18, Prime Loss Detection Method.
u
b6: Dwell Function
No.
(Addr.
Hex)
Name
Description
Values
Page
b6-01
(01B6) Dwell Reference at Start Dwell Ref @Start
Parameters b6-01 and b6-02 set the frequency to hold and the
time to maintain that frequency at start.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
b6-02
(01B7) Dwell Time at Start
Dwell Time @Start
Default: 0.0 s
Min.: 0.0
Max.: 10.0
–
b6-03
(01B8) Dwell Reference at Stop Dwell Ref @Stop
Parameters b6-03 and b6-04 set the frequency to hold and the
time to maintain that frequency at stop.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
b6-04
(01B9) Dwell Time at Stop
Dwell Time @Stop
Default: 0.0 s
Min.: 0.0
Max.: 10.0
–
u
b8: Energy Saving
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
b8-01
(01CC)
Energy Saving Control
Selection
Energy Save Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
b8-02
(01CD) Energy Saving Gain
Energy Save Gain
OLV
OLV
OLV
OLV
Sets the gain used for Energy Saving.
Default: 0.7
Min.: 0.0
Max.: 10.0
–
b8-03
(01CE) Energy Saving Control
Filter Time Constant
Energy Save F.T
OLV
OLV
OLV
OLV
Sets a time constant for Energy Saving.
Min.: 0.00 s
Max.: 10.00 s
–
b8-04
(01CF)
Energy Saving
Coefficient Value
Energy Save COEF
V/f
V/f
Determines the level of maximum motor efficiency. Setting
range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display
resolution depends on the rated output power of the drive.
Default:
Min.: 0.00
Max.: 655.00
–
b8-05
(01D0)
Power Detection Filter
Time
kW Filter Time
V/f
V/f
Sets a time constant filter for output power detection.
Default: 20 ms
Min.: 0
Max.: 2000
–
b8-06
(01D1)
Search Operation
Voltage Limit
Search V Limit
V/f
V/f
Sets the limit for the voltage search operation as a percentage of
the motor rated voltage.
Default: 0%
Min.: 0
Max.: 100
–
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
B.2 b: Application
262
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......