External Heatsink Installation, Finless Drive
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation b40 °C and
+50 °C requires output current derating.
100
85
70
55
0
L8-35 = 2: IP20/NEMA Type 1 Enclosure
L8-35 = 3: External Heatsink lnstallation
L8-35 = 0: IP00/Open-Chassis Enclosure
30
-10
40
50
Drive Rating
(%)
L8-12
(Ambient temp:
°
C)
L8-35 = 1: Side-by-Side Mounting
Figure A.1 Ambient Temperature and Installation Method Derating
u
Altitude Derating
The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive
rated voltage and the rated output current must be derated for 0.2% per 100 m.
A.4 Drive Derating Data