L8-40: Carrier Frequency Reduction Off Delay Time
Sets the delay time which is used to switch back to the normal carrier frequency. The carrier frequency reduction function is
disabled if this value is 0 s.
No.
Name
Setting Range
Default
L8-40
Low Carrier Frequency Off Delay Time
0.00 or 2.00 s
0.50 s
n
L8-41: High Current Alarm Selection
The drive can be set to trigger a high current alarm (HCA) when the output current rises too high.
No.
Name
Setting Range
Default
L8-41
High Current Alarm Selection
0 or 1
0
Setting 0: Disabled
No alarm is output.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output indicating an alarm
(H2-01/02/03 = 10) can be programmed.
5.8 L: Protection Functions