Table 5.3 Check to see if A1-01 is locked (continuing from step 10 above)
Step
Display/Result
1.
Press
to display A1-01.
“01” flashes
2.
Press
to display the value set to A1-01.
3.
Press
and
, making sure that the setting values cannot be changed.
4.
Press
to return to the first display.
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
Step
Display/Result
1.
Press
to enter the parameter setup display.
2.
Press
to select the flashing digits as shown.
“01” flashes
3.
Press
to scroll to A1-04.
4.
Enter the password “1234”.
5.
Press
to save the new password.
6.
Drive returns to the parameter display.
7.
Press
and scroll to A1-01.
8.
Press
to display the value set to A1-01. If the first "0" blinks, parameter settings
are unlocked.
9.
Use
and
to change the value if desired. This is not typical.
10.
Press
to save the setting, or
to return to the previous display without saving
changes.
11.
The display automatically returns to the parameter display.
Note:
Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the password to
“0000”. Reenter the password to parameter A1-05 after drive initialization.
u
A2: User Parameters
n
A2-01 to A2-32: User Parameters
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the
parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to this
list.
No.
Parameter Name
Setting Range
Default
A2-01 to A2-32
User Parameters 1 to 32
b1-01 to S6-02
Depending on
A1-03
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-01 = 2). Next
assign the parameter number to the User Parameters list by entering it into one of the A2-
oo
parameters. By then setting
A1-01 to “1”, the access level can be restricted so that users can only set and reference the specific parameters saved as User
Parameters.
n
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
5.1 A: Initialization
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
113
5
Parameter Details
Содержание iQpump Micro CIMR-PW Series
Страница 443: ......