VIPA System 200V 
 
 
 

IM | Manual 

HB97E_IM | 208-1DPx1 | Rev. 14/05 

 

 

 
 
 
 

Содержание IM 208-1DPx1

Страница 1: ...VIPA System 200V IM Manual HB97E_IM 208 1DPx1 Rev 14 05 ...

Страница 2: ...isions Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declaration of Conformity DoC please contact your local VIPA customer service organization Trademarks VIPA SLIO System 100V System 200V System 300V System 300S System 400V System 500S and Commander Compact are registered trademarks of VIPA Gesellschaft für Vi...

Страница 3: ...12 Installation guidelines 1 14 General data 1 17 Chapter 2 Hardware description 2 1 Properties 2 2 Structure 2 3 Technical data 2 6 Chapter 3 Deployment 3 1 Basics PROFIBUS 3 2 Operating modes and Start up behavior 3 10 Deployment Master with a CPU 21x 3 11 Project engineering 3 12 Slave operating mode 3 22 Overall reset 3 26 Firmware update 3 27 PROFIBUS installation guidelines 3 29 Commissionin...

Страница 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_208 1DPx1 Rev 14 05 ...

Страница 5: ...m consisting of System 200V components Besides the dimensions the general technical data of System 200V will be found Chapter 2 Hardware description Here the hardware components of the IM 208 1DPx1 are described The technical data are at the end of the chapter Chapter 3 Deployment This chapter contains a description of the PROFIBUS DP master modules IM 208 1DPx1 under PROFIBUS A short introduction...

Страница 6: ...pters Every chapter provides a self contained description of a specific topic The following guides are available in the manual an overall table of contents at the beginning of the manual an overview of the topics for every chapter The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Important passages in the text are highlighted by following icons an...

Страница 7: ... The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning the components described in this manual Hardware modifications to the process control system should only be carried out when the system has been disconnected from power Installation and hardware modificati...

Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_208 1DPx1 Rev 14 05 ...

Страница 9: ...formation required to assemble and wire a controller system consisting of System 200V components Besides the dimensions the general technical data of System 200V will be found Topic Page Chapter 1 Basics and Assembly 1 1 Safety Information for Users 1 2 System conception 1 3 Dimensions 1 5 Installation 1 7 Demounting and module exchange 1 11 Wiring 1 12 Installation guidelines 1 14 General data 1 ...

Страница 10: ...s thereby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices and meticulous attention to the applicable rules and regulations for handling the respective equipment can prevent failures of electros...

Страница 11: ...ion modules Power supplies Extension modules CPU 214 M P I PW SF FC MC R S RN ST MR MMC 2 1 2 DC 24V X1 VIPA 214 1BC03 X 2 3 4 PW ER RD DE IM 253DP ADR X 8 9 10 VIPA 253 1DP00 1 2 DC 24V X1 D P 9 9 With a head module CPU respectively bus interface and DC 24V power supply are integrated to one casing Via the integrated power supply the CPU respectively bus interface is power supplied as well as the...

Страница 12: ...re con nection facilities The modules are not connected to the backplane bus Profile rail 35mm Dimensions of the basic enclosure 1tier width HxWxD in mm 76x25 4x74 in inches 3x1x3 2tier width HxWxD in mm 76x50 8x74 in inches 3x2x3 Please note that you can only install head modules like the CPU the PC and couplers at slot 1 or 1 and 2 for double width modules 1 Head module double width 2 Head modul...

Страница 13: ...Rev 14 05 1 5 Dimensions 1tier width HxWxD in mm 76 x 25 4 x 74 2tier width HxWxD in mm 76 x 50 8 x 74 80 mm 60 mm 74 mm 88 mm ca 110 mm 84 mm 85 mm 76 62 mm 76 mm 2 77 cm 24 mm Dimensions Basic enclosure Installation dimensions Installed and wired dimensions In Output modules ...

Страница 14: ...em 200V 1 6 HB97E IM RE_208 1DPx1 Rev 14 05 84 46 mm 88 mm 4 66 mm 27 mm 8 cm 76 mm 24 mm 11 mm 85 mm 89 mm 89 mm 27 mm 8 cm 76 mm 12 cm 125 mm 91 mm 65 mm 24 mm 5 mm 11 mm 85 mm Function modules Extension modules CPUs here with EasyConn from VIPA ...

Страница 15: ... profile rail Length 2000mm height 15mm 290 1AF30 35mm profile rail Length 530mm height 15mm System 200V modules communicate via a backplane bus connector The backplane bus connector is isolated and available from VIPA in of 1 2 4 or 8tier width The following figure shows a 1tier connector and a 4tier connector bus The bus connector is to be placed on the profile rail until it clips in its place a...

Страница 16: ...de rails 1 Head module double width 2 Head module single width 3 Peripheral module PW ER RD BA ADR DC24V 1 2 0 1 1 2 4 3 PW SF FC MC MMC R S 4 Guide rails Use bus connectors as long as possible Sort the modules with a high current consumption right beside the head module In the service area of www vipa com a list of current consumption of every System 200V module can be found Installation on a pro...

Страница 17: ...ce of at least 60mm exists above and 80mm below the middle of the profile rail Every row must be completed from left to right and it has to start with a head module 1 Head module double width 2 Head module single width 1 2 4 3 3 Peripheral modules 4 Guide rails Modules are to be installed side by side Gaps are not permitted between the modules since this would interrupt the backplane bus A module ...

Страница 18: ...he outer left location with the installation of your head module and install the peripheral modules to the right of this 1 Head module double width 2 Head module single width 3 Peripheral module 1 2 4 3 4 Guide rails Insert the module that you are installing into the profile rail at an angle of 45 degrees from the top and rotate the module into place until it clicks into the profile rail with an a...

Страница 19: ...r and pulling the connector The casing of the module has a spring loaded clip at the bottom by which the module can be removed The clip is unlocked by pressing the screwdriver in an upward direction Withdraw the module with a slight rotation to the top Attention Power must be turned off before modules are installed or removed Please regard that the backplane bus is interrupted at the point where t...

Страница 20: ...o screw terminal connections spring clip wiring is vibration proof The assignment of the terminals is contained in the description of the respective modules You may connect conductors with a diameter from 0 08mm2 up to 2 5mm2 max 1 5mm2 for 18pole connectors The following figure shows a module with a 10pole connector 1 2 3 4 5 6 7 8 9 1 0 1 2 3 3 4 5 1 1 1 2 3 4 5 6 7 8 9 1 0 2 1 2 3 4 5 Locking l...

Страница 21: ...iring procedure from top view Insert a screwdriver at an angel into the square opening as shown Press and hold the screwdriver in the opposite direction to open the contact spring Insert the stripped end of the wire into the round opening You can use wires with a diameter of 0 08mm2 to 2 5mm2 1 5mm2 for 18pole connectors By removing the screwdriver the wire is connected safely with the plug connec...

Страница 22: ... interferencing the environment All System 200V components are developed for the deployment in hard industrial environments and fulfill high demands on the EMC Nevertheless you should project an EMC planning before installing the components and take conceivable interference causes into account Electromagnetic interferences may interfere your control via different ways Fields I O signal conductors ...

Страница 23: ...n Data lines must be laid isolated Analog lines must be laid isolated When transmitting signals with small amplitudes the one sided laying of the isolation may be favorable Lay the line isolation extensively on an isolation protected earth con ductor rail directly after the cabinet entry and fix the isolation with cable clamps Make sure that the isolation protected earth conductor rail is connecte...

Страница 24: ...ation one sided Then you only achieve the absorption of the lower frequencies A one sided isolation connection may be convenient if the conduction of a potential compensating line is not possible analog signals some mV res µA are transferred foil isolations static isolations are used With data lines always use metallic or metalized plugs for serial couplings Fix the isolation of the data line at t...

Страница 25: ...ons CageClamps at the front facing connector core cross section 0 08 2 5mm2 or 1 5 mm2 18pole plug Complete isolation of the wiring when modules are exchanged Every module is isolated from the backplane bus ESD Burst acc IEC 61000 4 2 IEC 61000 4 4 to level 3 Shock resistance acc IEC 60068 2 6 IEC 60068 2 27 1G 12G Class of protection IP20 Operating temperature 0 60 C Storage temperature 25 70 C R...

Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_208 1DPx1 Rev 14 05 ...

Страница 27: ...DPx1 Rev 14 05 2 1 Chapter 2 Hardware description Here the hardware components of the IM 208 1DPx1 are described The technical data are at the end of the chapter Topic Page Chapter 2 Hardware description 2 1 Properties 2 2 Structure 2 3 Technical data 2 6 Overview Contents ...

Страница 28: ...ts the data areas of the slaves located on the V bus into the addressing area of the CPU Project engineering by means of VIPAs WinNCS or Siemens SIMATIC Manager or ComPROFIBUS Diagnostic facilities IM 208 DP D P R E IF DE MC MMC VIPA 208 1DP01 X 2 3 4 RN ST MR IM 208 DPO R E IF DE MC MMC VIPA 208 1DP11 X 2 3 4 RN ST MR Type Order number Description IM 208DP VIPA 208 1DP01 PROFIBUS DP master with R...

Страница 29: ...4 2 3 IM 208 DP D P R E IF DE MC MMC VIPA 208 1DP01 X 2 3 4 RN ST MR 1 DP RS485 5 4 3 2 1 9 8 7 6 M5V reserved RxD TxD P line B RTS M5V P5V n c RxD TxD N line A n c 1 2 3 4 5 6 7 8 9 The VIPA PROFIBUS master is connected to your PROFIBUS network via the 9pin socket Please note that due to the system pin 2 of the PROFIBUS interface must not be connected Front view IM 208DP Interface RS485 interface...

Страница 30: ... 3 Slot for memory card 4 FO interface 4 2 3 IM 208 DPO R E IF DE MC MMC VIPA 208 1DP11 X 2 3 4 RN ST MR 1 LWL Rx 1 Tx 2 The IM 208DPO is connected to PROFIBUS by a FOL fiber optic link interface The layout of this interface is shown below Connect to receive line from slave Connect to send line to slave Front view IM 208DPO Interface FOL interface ...

Страница 31: ...ating mode selector is used to select the operating modes STOP ST RUN RN and MEMORY MR The master will change to RUN mode if the operating mode selector is set to RN and parameters are acceptable When the operating mode switch is set to ST the master will change to STOP mode In this mode all communication is terminated the outputs of the allocated slaves will be set to 0 and the master issues an a...

Страница 32: ...tions yes Diagnostics information read out possible Supply voltage display none Group error display red LED Channel error display none Functionality Sub D interfaces Type Type of interface RS485 Connector Sub D 9 pin female Electrically isolated 9 MPI MP I MPI RS232 DP master yes DP slave yes Point to point interface 5V DC Power supply max 90mA non isolated 24V DC Power supply Housing Material PPE...

Страница 33: ...parameterizable Diagnostic functions yes Diagnostics information read out possible Supply voltage display none Group error display red LED Channel error display none Functionality Sub D interfaces Type Type of interface FOC Connector 2 pin FOC POF HCS Electrically isolated 9 MPI MP I MPI RS232 DP master yes DP slave yes Point to point interface Housing Material PPE Mounting Profile rail 35 mm Mech...

Страница 34: ...x no of input bytes 256 1024 since V3 0 0 max no of output bytes 256 1024 since V3 0 0 PROFIBUS interface Connection 2pin socket for fiber optic cable Network topology Linear structure with dual FO cable no bus terminator required Medium dual core fiber optic cable Data transfer rate 12MBaud Total length at POF FO max 50m between stations at HCS FO max 300m between stations Max no of stations 17 s...

Страница 35: ...FIBUS master modules that are available from VIPA The chapter concludes with a number of communication examples and the technical data Topic Page Chapter 3 Deployment 3 1 Basics PROFIBUS 3 2 Operating modes and Start up behavior 3 10 Deployment Master with a CPU 21x 3 11 Project engineering 3 12 Slave operating mode 3 22 Overall reset 3 26 Firmware update 3 27 PROFIBUS installation guidelines 3 29...

Страница 36: ...specific diagnostic PROFIBUS DP is a special protocol intended mainly for automation tasks in a manufacturing environment DP is very fast offers Plug n Play facilities and provides a cost effective alternative to parallel cabling between PLC and remote I O PROFIBUS DP was designed for high speed cyclical data communication between bus master and slave systems The original version designed DP V0 ha...

Страница 37: ...ansfer data between the System 200V periphery and the high level master In accordance with the PROFIBUS standards these devices have no bus access rights They are only allowed to acknowledge messages or return messages to a master when this has issued a request Slaves are also referred to as passive participants The master of the class 1 is a central control that exchanges cyclically information w...

Страница 38: ...ta transfer phase the master checks whether the defined configuration corresponds with the actual configuration This check is performed during the definition and configuration phase The verification includes the device type format and length information as well as the number of inputs and outputs In this way a reliable protection from configuration errors is achieved The master handles the transfe...

Страница 39: ...ions for fast error localization Diagnostic messages are transferred via the bus and collected by the master As a further function the device specific diagnostic of the DP V1 have been enhanced and divided into the categories alarms and status messages DP V0 provides the basic functionality of DP including cycle data exchange as well as station diagnostic module diagnostic and channel specific dia...

Страница 40: ...er receive and the data in the buffer send is transferred into the PROFIBUS output area The exchange of data between DP master and DP slave is completed cyclically and it is independent from the V bus cycle To ensure that the data transfer is synchronized the V bus cycle time should always be less than or equal to the DP cycle time The parameter min_slave_interval 3ms is located in the GSD file VI...

Страница 41: ...e 2 Slave 3 The DPM 1 Master Class 1 has the token and is able to send messages to or retrieve them from slave 1 then slave 2 etc in a fixed sequence until it reaches the last slave of the current list MS0 channel it then passes on the token to the DPM 2 Master Class 2 This master can then use the remaining available time gap of the programmed cycle to set up an acyclic connection to any slave e g...

Страница 42: ...p by the DPM 1 and is closely linked to the connection for cyclic data communication It can be used by the master that has parameterized and configured the respective slave Services for Acyclic data communication between the DPM 2 and Slaves Initiate Abort Setup and termination of a connection for acyclic data communication between the DPM 2 and the Slave Read The master reads a data block from th...

Страница 43: ...fferent stages Extensions to the system do not affect stations that have already been commissioned Any failures of stations or new devices are detected automatically The fiber optic system employs pulses of monochromatic light The optical waveguide is not susceptible to external electrical interference Fiber optic systems have a linear structure Each device requires two lines a transmit and a rece...

Страница 44: ...d DP master changes to RUN mode The DP master interface shows this status by means of the LEDs R and DE With incorrect parameters the DP master remains in STOP state and shows an error in parameterization by means of the IF LED The DP master will then be active on the bus with the following default bus parameters Default bus parameters Address 2 Communication rate 1 5MBaud Note With DP master firm...

Страница 45: ...ing alarms causing the CPU to call the according OBs Process alarm OB40 Diagnostic alarm OB82 Slave failure OB86 As soon as the BASP signal i e Befehlsausgabesperre command output lock comes from the CPU the IM 208 sets the outputs of the connected periphery to zero Note After a slave failure the process image of the inputs is in the same state than before the failure At deployment of the IM 208 P...

Страница 46: ...ct engineering with VIPA WinNCS respectively ComPROFIBUS from Siemens and export as 2bf file The file is transferred by MMC respectively SIP Tool and Green Cable to the DP master With a overall reset sequence the project is transferred to the Flash ROM of the DP master V Bus to 1 DP Master PC CPU DP Master MMC MPI DP MMC RN ST MR Flash ROM Tip 3Sec Green Cable RS232 Green Cable 2bf file wld file H...

Страница 47: ...master in the hardware catalog at Simatic300 CPU 300 CPU315 2DP 6ES7 315 2AF03 0AB0 V1 2 3 Assign a PROFIBUS address 2 or higher to your master 4 Click at DP select the operating mode DP master at Object properties and confirm your entry with OK 5 With a right click on DP a context menu opens Choose Insert master system Create a new PROFIBUS subnet via NEW The following picture shows the new maste...

Страница 48: ...modules from the hardware catalog at VIPA_CPU21x to the slots following the CPU Start with slot 1 The same is to do for the DP master place holder 8 For projecting DP slaves connected to the DP master select the VIPA_DP200V_2 system Select the according PROFIBUS system in the hardware catalog and drag it to the DP master subnet Assign an address 2 to the slave Set the according modules at slot 0 b...

Страница 49: ...AF03 0AB0 V1 2 3 Assign a PROFIBUS address 2 or higher to your master 4 Click at DP select the operating mode DP master at Object properties and confirm your entry with OK 5 With a right click on DP a context menu opens Choose Insert master system Create a new PROFIBUS subnet via NEW 6 To configure DP salves which are connected to the DP master select the VIPA_DP200V_2 system Select the according ...

Страница 50: ...rs at the same backplane bus with one MMC 8 Create with File Memory Card File New a new wld file This need to have the file name dpm wld to be recognized from the PROFIBUS master This file is additionally shown to the configuration window 9 Go into your project into the directory modules and copy the directory System data into the created dpm wld file If an already existing System data directory s...

Страница 51: ...l module that is connected to the corresponding slave via the backplane bus You can select automatic addressing for the periphery by clicking Auto and display allocated addresses by means of MAP Please take care that the automatic address allocation does not cause conflicts with the local periphery For intelligent modules like the CP 240 the configurable parameters will be displayed 6 When you hav...

Страница 52: ...at compatible modules from VIPA Please regard the instructions to the Green Cable further down At deployment of the Green Cable from VIPA the MPI interface has to be configured PC Adapter MPI 38400Baud 2 Switch your DP master to RUN 3 Switch on the power supply of the CPU 4 Transfer your project into the CPU with PLC Load to module in the hardware configurator from Siemens At Power ON the CPU alwa...

Страница 53: ...uring data transfer all LEDs extinguish At successful data transfer the green R LED blinks 3 times At error the red E LED blinks 3 times RN ST MR RN ST MR RN ST MR Transfer Tip R E IF DE MC R E IF DE MC R E IF DE MC R E IF DE MC R E IF DE MC RN ST MR 3Sec R E IF DE MC RN ST MR RN ST MR OK Error 3x 3x 6 Now you may release the MMC again Transfer via MMC IM 208 DP D P R E IF DE MC MMC RN ST MR 7 Swi...

Страница 54: ...e g a visualization system execute firmware updates of the CPUs and fieldbus masters Via the Green Cable and an upload application you may update the firmware of all recent VIPA CPUs with MP2 I jack and certain fieldbus masters see Note Important notes for the deployment of the Green Cable Nonobservance of the following notes may cause damages on system components For damages caused by nonobservan...

Страница 55: ...urn on your PC and start the SIP tool that is supplied with WinNCS Select the appropriate COM port and establish a connection by means of Connect When the connection has been established the SIP tool will display OK in the status line located at the top otherwise an ERR message will be displayed 4 Click Download select your dpm 2bf res dpm wld file and transfer this file into the DP master 5 Termi...

Страница 56: ... 2DP with virtual PROFIBUS slave address 1 for System 200V The DP slave contains CPU 21x I O periphery and IM 208DP set parameter Transfer project to IM 208 to No Project is to be transferred to the CPU 21x 2 Hardware configuration IM 208DP Project engineering IM 208DP as Siemens CPU 315 2DP with Slave Operation of the DP part Use Properties to set PROFIBUS address and I O area and transfer the pr...

Страница 57: ... drag and drop the according System 200V modules from the hardware catalog at VIPA_CPU21x to the slot following the CPU Start with slot 1 The same is to do for the DP master substitute Set at the IM 208DP properties the parameter Transmit project to IM 208 to No So the CPU can not overwrite the recent local stored DP slave project in the IM 208DP Transfer the project to the CPU The employment of t...

Страница 58: ...ion type S7 315 2DP This is to be found in the hardware catalog at PROFIBUS DP Additional field devices PLC SIMATIC S7 315 2DP Assign the PROFIBUS address to the DP slave that you ve parameterized at the slave For the PROFIBUS communication create the same I O range that you ve parameterized at the slave in form of modules Please regard that a slave output area relates to a master input area and v...

Страница 59: ... DP Operating mode DP master General Properties PROFIBUS address 2 125 which is still unused Hardware configuration System 200V VIPA_21x GSD required 0 1 CPU 21x I O periphery and IM 208DP Transfer project to CPU 21x General PROFIBUS PROFIBUS address 1 Transfer project to IM 208DP General Properties PROFIBUS address like hardware configuration IM 208DP Operating mode DP master Addresses Diagnostic...

Страница 60: ...n 3s once more in pos MR The content of the Flash ROM is deleted The operation has been executed properly when the green R LED blinks 3 times and the IF LED is permanent on Clear R E IF DE MC R E IF DE MC R E IF DE MC R E IF DE MC R E IF DE MC R E IF DE MC RN ST MR OK 3x RN ST MR 3s 3x RN ST MR Tip R E IF DE MC R E IF DE MC 3x RN ST MR 9s max 3s As soon as you switch the master to RUN this boots a...

Страница 61: ...stroy the DP master for example if the voltage supply is interrupted during transfer or if the firmware file is defective In this case please call the VIPA Hotline Please regard that the version of the update firmware has to be different from the existing firmware otherwise no update is executed A label on the rear of the DP master module indicates the firmware version Go to www vipa com Click on ...

Страница 62: ...ware file has been found on the MMC You start the transfer of the firmware as soon as you tip the RUN STOP lever downwards to MRES within 10s The CPU shows the transfer via a LED blink line During the update process the LEDs SF FC and MMC are alternately blinking This may last several minutes The update is successful finished when all CPU LEDs are on If they are blinking fast an error occurred Aft...

Страница 63: ...y on the baud rate Only one fiber optic master may be used on one line Multiple masters may be deployed with a single CPU as long as they are located on the same backplane bus please take care not to exceed the max current consumption The maximum length of a FO link between two slaves may not exceed 300m with HCS FO and 50m with POF FO independent from the baud rate The number of bus participants ...

Страница 64: ...le based upon the RS485 interface The RS485 interface is working with voltage differences Though it is less irritable from influences than a voltage or a current interface You are able to configure the network as well linear as in a tree structure Max 32 participants per segment are permitted Within a segment the members are linear connected The segments are connected via repeaters The maximum seg...

Страница 65: ...te The PROFIBUS line has to be terminated with its ripple resistor Please make sure to terminate the last participants on the bus at both ends by activating the terminating resistor In PROFIBUS all participants are wired parallel For that purpose the bus cable must be feed through Via the order number VIPA 972 0DP10 you may order the bus connector EasyConn This is a bus connector with switchable t...

Страница 66: ...erminating resistor 1 last bus participant further participants Attention The terminating resistor is only effec tive if the connector is installed at a bus participant and the bus participant is connected to a power supply Note A complete description of installation and deployment of the terminating resistors is delivered with the connector Loosen the screw Lift contact cover Insert both wires in...

Страница 67: ... the manufacturers guidelines it is not susceptible to external electrical interference Fiber optic systems have a linear structure Each device requires two lines a transmit and a receive line dual core It is not necessary to provide a terminator at the last device The PROFIBUS FO network supports a maximum of 126 devices including the master The maximum distance between two devices is limited to ...

Страница 68: ...for successor reception transmission 7mm Pressring Crimp pressring here with crimping tool Cut protruding fiber using a knife to leave app 1 5 mm Polish the ends to a flat surface using the HP polishing set 1 5 mm Advantages polarity protection You can only install the connector so that the side of the connector shown here faces to the right Disadvantages special tool required You require a specia...

Страница 69: ... protection against polarity reversal These plugs can be inserted in two positions Please check the polarity when you have turned on the power The light emitting fiber is the fiber for reception Assembling a plug 2 complete plugs are required to as semble a duplex plug Separate the two cores for a distance of app 5cm Use a stripper to remove the protection cover so that app 7mm of the fiber is vis...

Страница 70: ...re not connect modules that are able to issue alarms IM 253 1 Input output periphery IM 253 2 Input output periphery IM 253 4 Input output periphery IM 253 5 Input output periphery CPU IM 208 1 2 3 4 IM 208 5 IM 253 3 Input output periphery CPU with short cycle time subject to fast updates For short CPU cycle times the data of IM interface no 5 is always up to date slow due to the large number of ...

Страница 71: ...put periphery IM 253 2 Input output periphery IM 253 3 Input output periphery CPU IM 208 2 4 IM 253 4 Input output periphery IM 253 5 Input output periphery Expansion options master only by means of electrical connections slaves by means of electrical or optical connections Expansion options master only by means of electrical connections slaves by means of electrical or optical connections Multi m...

Страница 72: ...4 IM 253 1 Input output periphery IM 253 2 Input output periphery IM 253 4 Input output periphery IM 253 3 Input output periphery Links to other masters via optical or electrical links by means of an optical link plug are NOT permitted Expansion options slaves optical slaves electric Optical PROFIBUS ...

Страница 73: ...2 4 IM 253 2 Input output periphery IM 253 3 Input output periphery B A A B IM 253 4 Input output periphery IM 253 5 Input output periphery Expandable by master only electrical slaves electrical Bus connector RS 485 This bus connector is provided to allow connection of an optical via OLP or electrical device to the PROFIBUS line OLP Optical Link Plug The OLP provides the interface between the opti...

Страница 74: ...of every PROFIBUS slave module as required Configure your PROFIBUS master in your master system You can use the WinNCS of VIPA for this purpose A number of different transfer methods are employed due to the fact that a number of different hardware versions of the VIPA PROFIBUS master modules are existing These transfer methods are described in the master configuration guide for the respective hard...

Страница 75: ...fferent types of network interruption Interruption at position A The PROFIBUS has been interrupted Interruption at position B Communication via the backplane bus has been interrupted LED Slave 1 Position of interruption LED A B RD blinks off ER off on DE off off A B Slave 1 Slave 2 Master LED Slave 2 Position of interruption LED A B RD blinks on ER off off DE off on ...

Страница 76: ...a PROFIBUS and monitored at the output module The counter values have to be created in the CPU The CPU has to count from FFh to 00h and transfer the counter value cyclically into the output area of the PROFIBUS master The master sends this value to the DP slave The received value shall be monitored at the output module at address 0 CPU 214 Count Counter FFh 00h IM208DP C DO 8 C CPU Master Addr 2 I...

Страница 77: ...ress 2 Add a PROFIBUS slave VIPA_CPU21x with address 1 Include the CPU 214 1BA03 at slot 0 Include the DP master 208 1DP01 at slot 1 To connect your IM 253DP you have to execute the following steps after including the GSD file vipa0550 gsd Add the PROFIBUS slave VIPA_DP200V_2 with address 3 You will find the DP slave in the hardware catalog from Siemens at PROFIBUS DP Additional field devices I O ...

Страница 78: ... only be used with VIPA CPUs of the Systems 100V 200V 300V and 500V For the employment the following settings are required Choose the interface parameterization PC Adapter MPI in your project engineering tool at Options Configure PU PC interface If needed you have to add this first Click on Properties and set the wanted COM port and the baud rate 38400 at Local interface Configure the MPI interfac...

Страница 79: ... bus at the output module at address 0 Vice versa the CPU 214DP has to count from 00h to FFh store the value in the output area of the CPU slave and transfer it to the master via PROFIBUS This value is monitored at the output module of the CPU 214 address 0 CPU 214DP DO 8 C2 C1 Counter C2 00h FFh Addr 3 Slave CPU 214 DO 8 C1 C2 Counter C1 FFh 00h C1 C2 Master IM208DP Addr 2 CPU 214 and DP master C...

Страница 80: ...de a CPU 214 1BA03 at slot 0 of the slave system Include the DP master 208 1DP01 place holder at slot 1 and include the output module 222 1BF00 at slot 2 Give the output module 222 1BF00 at slot 0 To connect your real CPU 214DP you have to execute the following steps after including the GSD file vipa04d5 gsd Add the PROFIBUS slave VIPA_CPU2xxDP address 3 Include the 2 Byte Output element at slot 0...

Страница 81: ...ata transfer via PROFIBUS L IB 11 load input byte 11 output data of the CPU214DP and T QB 0 transfer to output byte 0 BE Read counter value from MB 0 decrement it store in MB 0 and transfer it to the CPU 21xDP via PROFIBUS OB 35 Time OB L MB 0 counter from 0xFF to 0x00 L 1 I T MB 0 T QB 21 Transfer to output byte 21 input data of the CPU214DP BE Transfer your project with the hardware configuratio...

Страница 82: ...e GSD file vipa_21x gsd Project a CPU 315 2DP with DP master master address 2 Add a PROFIBUS slave VIPA_CPU21x with address 1 Include the CPU 214 2BP03 at slot 0 Select the following parameters for the CPU 214DP Input Add 30 Input Length 2 Output Add 40 Output Length 2 Prm Add 800 Diag Add 900 Stat Add 1020 PROFIBUS DP Add 3 Include the output module 222 1BF00 at slot 1 and give them the output ad...

Страница 83: ...valid L B 16 FE control byte for Master CPU T PQB 40 Data transfer via PROFIBUS L PIB 31 load periphery byte 31 input data from PROFIBUS slave and T IB 0 transfer into output byte 0 BE Read counter value from MB 0 increment it store it in MB 0 and transfer it via PROFIBUS to CPU 214 OB 35 Time OB L MB 0 counter from 0x00 to 0xFF L 1 I T MB 0 T PQB 41 Transfer counter value to periphery byte 41 Out...

Страница 84: ...Chapter 3 Deployment Manual VIPA System 200V 3 50 HB97E IM RE_208 1DPx1 Rev 14 05 ...