IM | 053-1PN00 | Manual
HB300 | IM | 053-1PN00 | en | 19-08
VIPA System SLIO
Interface module PROFINET - IM 053PN
www.vipa.com/en/service-support/manuals
Страница 1: ...IM 053 1PN00 Manual HB300 IM 053 1PN00 en 19 08 VIPA System SLIO Interface module PROFINET IM 053PN www vipa com en service support manuals ...
Страница 2: ...053 1PN00_000_IM 053PN 3 EN 2019 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 49 9132 744 0 Fax 49 9132 744 1864 Email info vipa com Internet www vipa com ...
Страница 3: ...g LEDs 32 2 8 Installation guidelines 33 2 9 General data 35 3 Hardware description 37 3 1 Properties 37 3 2 Structure 38 3 2 1 Interfaces 38 3 2 2 LEDs 39 3 2 3 Address switch 41 3 3 Technical data 43 4 Deployment 45 4 1 Basics PROFINET 45 4 2 PROFINET installation guidelines 47 4 3 Accessing the System SLIO 49 4 3 1 Overview 49 4 3 2 Accessing the I O area 50 4 3 3 Accessing the parameter data 5...
Страница 4: ...4 7 2 Diagnostic interrupt 64 4 8 I M data 71 4 9 Index overview 73 VIPA System SLIO Table of contents HB300 IM 053 1PN00 en 19 08 4 ...
Страница 5: ...s may be included for units which are not present at the customer site The exact scope of delivery is described in the respective purchase contract Hereby VIPA GmbH declares that the products and systems are in compliance with the essential requirements and other relevant provisions Conformity is indicated by the CE marking affixed to the product For more information regarding CE marking and Decla...
Страница 6: ...IPA It contains a description of the structure project engineering and deployment Product Order number as of state HW FW IM 053PN 053 1PN00 04 V1 5 7 The manual is targeted at users who have a background in automation technology The manual consists of chapters Every chapter provides a self contained description of a specific topic The following guides are available in the manual n An overall table...
Страница 7: ...nnel in the n project design department n installation department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in this manual Hardware modifications to the process control system should only be carried out when the system has been disconnected from power Installation and hardware modifications only by properly trai...
Страница 8: ... that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices and meticulous attention to the applicable rules and regulations for handling the respective equipment can prevent failures of electrostatic sensitive modules Modules must be shipped in the original packi...
Страница 9: ...lexity is low because the supply of the DC 24V power section is integrated to the backplane bus and defective modules may be replaced with standing wiring By deployment of the power modules in contrasting colors within the system further isolated areas may be defined for the DC 24V power section supply respectively the electronic power supply may be extended with 2A VIPA System SLIO Basics and mou...
Страница 10: ...dules are supplied The DC 24 power section supply for the linked periphery modules is established via a further connection of the power module By installing of up to 64 periphery modules at the backplane bus these are electrically connected this means these are assigned to the backplane bus the elec tronic modules are power supplied and each periphery module is connected to the DC 24V power sectio...
Страница 11: ...dule contains the backplane bus with power supply for the electronic the DC 24V power section supply and the staircase shaped terminal for wiring Additionally the terminal module has a locking system for fixing at a mounting rail By means of this locking system your SLIO system may be assembled outside of your switchgear cabinet to be later mounted there as whole system The functionality of a SLIO...
Страница 12: ...e mounting a System SLIO module For the protection of the backplane bus con nector you always have to mount the bus cover at the last module of your system again The bus cover has the order no 000 0AA00 There is the possibility to fix the assignment of electronic and terminal module Here coding pins order number 000 0AC00 from VIPA can be used The coding pin consists of a coding jack and a coding ...
Страница 13: ...This is always located under the labeling strip of the corresponding electronic module n On modules without labeling strip such as CPUs the hardware revision is printed on the front The example here shows the hardware revision 1 1 is marked with X On the CPUs and some bus couplers you can output the hardware revision HW Revision via the integrated web server 2 3 Dimensions Hardware revision on the...
Страница 14: ...Dimensions CPU 01x Dimensions bus coupler and line extension slave Dimensions line extension master VIPA System SLIO Basics and mounting Dimensions HB300 IM 053 1PN00 en 19 08 14 ...
Страница 15: ...ail The bus coupler is fixed to the mounting rail by pushing downward the locking levers The bus coupler is directly mounted at a mounting rail Up to 64 modules may be mounted The electronic and power section supply are connected via the back plane bus Please consider here that the sum current of the electronic power supply does not exceed the maximum value of 3A By means of the power module 007 1...
Страница 16: ... at least 80mm above and 60mm below respectively 80mm by deployment of shield bus carriers exist 2 Turn the locking lever upwards place the bus coupler at the mounting rail and turn the lever downward Proceeding VIPA System SLIO Basics and mounting Mounting bus coupler HB300 IM 053 1PN00 en 19 08 16 ...
Страница 17: ...the periphery modules you want 3 After mounting the whole system to protect the backplane bus connectors at the last module you have to mount the bus cover now If the last module is a clamp module for adaptation the upper part of the bus cover is to be removed Mounting periphery modules VIPA System SLIO Basics and mounting Mounting bus coupler HB300 IM 053 1PN00 en 19 08 17 ...
Страница 18: ...her than SELV PELV specification must be separated from the system s equipment 2 5 1 Wiring bus coupler The System SLIO bus coupler have a power module integrated Terminals with spring clamp technology are used for wiring The spring clamp technology allows quick and easy connection of your signal and supply lines In contrast to screw terminal connections this type of connection is vibration proof ...
Страница 19: ...rt the stripped end of wire into the round opening You can use wires with a cross section of 0 08mm2 up to 1 5mm2 3 By removing the screwdriver the wire is securely fixed via the spring contact to the terminal 1 DC 24V for power section supply I O area max 10A 2 DC 24V for electronic power supply bus coupler and I O area Wiring procedure Standard wiring VIPA System SLIO Basics and mounting Wiring ...
Страница 20: ... n The power section supply is to be externally protected with a fuse which corresponds to the maximum current This means max 10A is to be protected with a 10A fuse fast respectively by a line circuit breaker 10A characteristics Z n It is recommended to externally protect the electronic power supply for bus coupler and I O area with a 2A fuse fast respectively by a line circuit breaker 2A characte...
Страница 21: ...ach the cables with the accordingly stripped cable screen and fix it by the shield clamp with the shield bus 2 5 2 Wiring periphery modules CAUTION Do not connect hazardous voltages If this is not explicitly stated in the corresponding module description hazardous voltages are not allowed to be connected to the corresponding terminal module With wiring the terminal modules terminals with spring cl...
Страница 22: ...ring contact to the terminal 1 Shield bus carrier 2 Shield bus 10mm x 3mm 3 Shield clamp 4 Cable shield To attach the shield the mounting of shield bus carriers are necessary The shield bus carrier available as accessory serves to carry the shield bus to connect cable shields 1 Each System SLIO module has a carrier hole for the shield bus carrier Push the shield bus carrier until they engage into ...
Страница 23: ...wer modules terminals with spring clamp technology are used for wiring The spring clamp technology allows quick and easy connection of your signal and supply lines In contrast to screw terminal connections this type of connection is vibration proof Umax 30V DC Imax 10A Cross section 0 08 1 5mm2 AWG 28 16 Stripping length 10mm Terminal module terminals Data VIPA System SLIO Basics and mounting Wiri...
Страница 24: ...t the stripped end of wire into the round opening You can use wires with a cross section of 0 08mm2 up to 1 5mm2 3 By removing the screwdriver the wire is securely fixed via the spring contact to the terminal 1 DC 24V for power section supply I O area max 10A 2 DC 24V for electronic power supply bus coupler and I O area Wiring procedure Standard wiring VIPA System SLIO Basics and mounting Wiring W...
Страница 25: ... The power section supply is to be externally protected with a fuse which corresponds to the maximum current This means max 10A is to be protected with a 10A fuse fast respectively by a line circuit breaker 10A characteristics Z n It is recommended to externally protect the electronic power supply for head modules and I O area with a 2A fuse fast respectively by a line circuit breaker 2A character...
Страница 26: ...ith max 4A n By placing the power module 007 1AB10 at the following backplane bus modules may be placed with a sum current of max 2A Afterwards a power module is to be placed again To secure the power supply the power modules may be mixed used 1 DC 24V for power section supply I O area max 10A 2 DC 24V for electronic power supply bus coupler and I O area 3 DC 24V for power section supply I O area ...
Страница 27: ...or adaptation to a flat mounting rail you may remove the spacer of the shield bus car rier 2 Put your shield bus into the shield bus carrier 3 Attach the cables with the accordingly stripped cable screen and fix it by the shield clamp with the shield bus 2 6 Demounting 2 6 1 Demounting bus coupler CAUTION Bus interface and power module may not be separated Here you may only exchange the electronic...
Страница 28: ...us coupler and pull it forward 4 Turn all the locking lever of the bus coupler to be exchanged upwards 5 Pull the bus coupler forward 6 For mounting turn all the locking lever of the bus coupler to be exchanged upwards 7 To mount the bus coupler put it to the left periphery module and push it guided by the stripes to the mounting rail 8 Turn all the locking lever downward again VIPA System SLIO Ba...
Страница 29: ... side until this engages to the terminal module ð Now you can bring your system back into operation 1 Power off your system 2 Remove if exists the wiring of the module 3 For demounting and exchange of a head module or a group of modules due to mounting reasons you always have to remove the electronic module right beside After mounting it may be plugged again Press the unlocking lever at the lower ...
Страница 30: ...e 10 Wire your module ð Now you can bring your system back into operation 1 Power off your system 2 Remove if exists the wiring of the module group 3 For demounting and exchange of a head module or a group of modules due to mounting reasons you always have to remove the electronic module right beside After mounting it may be plugged again Press the unlocking lever at the lower side of the just mou...
Страница 31: ...group put it to the gap between the both modules and push it guided by the stripes at both sides to the mounting rail 8 Turn all the locking lever downward again 9 Plug again the electronic module which you have removed before 10 Wire your module group ð Now you can bring your system back into operation VIPA System SLIO Basics and mounting Demounting Demounting periphery modules HB300 IM 053 1PN00...
Страница 32: ...ng power modules page 23 Behaviour After PowerON the MF LED of one module respectively more modules flashes The RUN LED remains off Reason At this position a module is placed which does not correspond to the configured module Remedy Match configuration and hardware structure Behaviour After PowerON all of the RUN LEDs up to the defective module are flashing With all following modules the MF LED is...
Страница 33: ...to the interference cause interferences to your control occur by means of different coupling mechanisms There are n galvanic coupling n capacitive coupling n inductive coupling n radiant coupling In the most times it is enough to take care of some elementary rules to guarantee the EMC Please regard the following basic rules when installing your PLC n Take care of a correct area wide grounding of t...
Страница 34: ...th conductor is impedance low because otherwise the interference currents may appear as interference cause When isolating cables you have to regard the following n If possible use only cables with isolation tangle n The hiding power of the isolation should be higher than 80 n Normally you should always lay the isolation of cables on both sides Only by means of the both sided connection of the isol...
Страница 35: ...ulation voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14 25 70 C Operation Horizontal installation hanging EN 61131 2 0 60 C Horizontal installation lying EN 61131 2 0 55 C Vertical installation EN 61131 2 0 50 C Air humidity EN 60068 2 30 RH1 without co...
Страница 36: ...y 2 EN 61000 4 3 HF field immunity casing 80MHz 1000MHz 10V m 80 AM 1kHz 1 4GHz 2 0GHz 3V m 80 AM 1kHz 2GHz 2 7GHz 1V m 80 AM 1kHz EN 61000 4 6 HF conducted 150kHz 80MHz 10V 80 AM 1kHz EN 61000 4 4 Burst degree of severity 3 EN 61000 4 5 Surge degree of severity 3 Due to the high energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like c...
Страница 37: ... electronic section supply of the periphery modules n Supports MRP slave Media Redundancy Protocol as MRP client n Supports shared device with up to 3 connections n Supports FMM Free Module Mapping n Supports multiple and single write acyclic communication n Integrated Web server n Integrated DHCP client Type Order number Description IM 053PN 053 1PN00 PROFINET IO device for System SLIO 053 1PN00 ...
Страница 38: ... supply 8 Power module 9 X1 PROFINET RJ45 bus interface P1 10 X2 PROFINET RJ45 bus interface P2 11 Unlocking lever power module 12 Bus interface 13 Terminal 14 Address selector 3 2 1 Interfaces CAUTION Bus interface and power module of the bus coupler may not be sepa rated Here you may only exchange the electronic module 053 1PN00 VIPA System SLIO Hardware description Structure Interfaces HB300 IM...
Страница 39: ...ssover transmission and receipt lines are automatically crossed if neces sary 3 2 2 LEDs PWR IO green PWR green PF red Description X Power section supply OK Electronic section supply OK X X Fuse electronic section supply defective not relevant X LED Color Description PWR green Bus interface is power supplied SF red System error Error at PROFINET or System SLIO bus BF red Bus error Error in PROFINE...
Страница 40: ...dule failure bus faulted n Error during firmware update shortly visible then restart 2Hz X X X Error IP address n There was not assigned a valid IP address n The assigned IP address already exists in the system X 1Hz 1Hz X X X X A firmware update is in progress Here BF and MT flash alternately X X X 2Hz X 2Hz X Identification via DCP Depending on the connection LNK1 or LNK2 are flashing with 2Hz f...
Страница 41: ...led n 1 enabled 2 20 1 PROFINET name VIPA053 1PN00 xxx with xxx decimal value of position 2 8 3 21 2 4 22 4 5 23 8 6 24 16 7 25 32 8 26 64 Essential switch settings Position State Behavior at start up 1 1 n DHCP client is activated n The IP address data are requested via DHCP n The IP address data are not stored in the flash respectively 1 DHCP offer is used n DHCP client is disabled if the 1 new ...
Страница 42: ...address to the PROFINET device by means of an initialization Otherwise this can not be found by the PROFINET controller 2 8 1 127 n PROFINET name device name VIPA053 1PN00 xxx with xxx decimal value of position 2 8 20 26 n Enter within your project a PROFINET name into the properties of the PROFINET device and set the same name at the address switch Here the IP address parameters may also be prese...
Страница 43: ...isplay yes Interrupts yes parameterizable Process alarm yes parameterizable Diagnostic interrupt yes parameterizable Diagnostic functions yes parameterizable Diagnostics information read out possible Supply voltage display green LED Service Indicator yellow LED Group error display red SF LED Channel error display none Hardware configuration Racks max 1 Modules per rack max 64 Number of digital mod...
Страница 44: ...ut bytes Parameter bytes Diagnostic bytes Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 48 5 mm x 109 mm x 76 5 mm Net weight 167 5 g Weight including accessories 167 5 g Gross weight 185 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes VIPA System SLIO...
Страница 45: ...et Here the provider sends its data without a request of the communication partner n Apart from the user data exchange also functions for parametrization and diagnostics are supported n PROFINET CBA means Component Based Automation n This component model describes the communication between autonomously working stations n It makes a simple modularization of complex plants possible by distributed in...
Страница 46: ...device which is connected to PROFINET The IO device is equal to the slave of PROFIBUS n IO supervisor The IO supervisor is an engineering station as e g programming unit PC or HMI interface for commissioning and diagnostics AR Application Relation corresponds to a connection to an IO controller or IO super visor n API means Application Process Identifier and defines besides Slot and Subslot a fur ...
Страница 47: ...rial environment The increased networking of entire industrial systems to the network levels within the company together with the functions of remote mainte nance have all served to increase vulnerability n Threats can arise from internal manipulation like technical errors operator and pro gram errors respectively from external manipulation like software viruses and worms trojans and password phis...
Страница 48: ...ET device n If a communication member fails communication across the failed member is no longer possible n If you connect communication devices to a switch with more tan 2 PROFINET ports you automatically create a star network topology n If an individual PROFINET device fails this does not automatically lead to failure of the entire network in contrast to other structures It is only if a switch fa...
Страница 49: ...FINET Device HW 04 n Please install the GSDML file in your configuration tool n More information about installing the GSDML file may be found at the manual of the according engineering tool n Structure and content of the GSDML file are defined by IEC 61158 n To set respectively change parameters during runtime there are according handling blocks for record set read write necessary n There are the ...
Страница 50: ...to the device as defined in the GSDML file n After a connection setup there is the possibility to read parameters from a module with SFC 52 RDREC and to write parameters to a module with SFC 53 WRREC n The parameters are activated as soon as they where written Access Slot subslot always 1 Index All parameters of the PROFINET IO device incl header 4byte 0 007Dh can also be addressed via 007Eh All p...
Страница 51: ...ring a hardware configuration is established within a PROFINET engineering tool like the Siemens SIMATIC Manager Here you assign the according IO device to the IO controller n A direct assignment takes place via the PROFINET device name that you set at the IO device with its address selector and the properties of the IO device n By installing the corresponding GSDML file the IM 053 1PN00 PROFINET ...
Страница 52: ...eset The PROFINET name preset at the address switch must always be identical to the device name in your project The address switch serves for the following settings n Selection of the address usage n Presetting of the PROFINET name Position Description 1 DHCP client n 0 disabled n 1 enabled 2 20 1 PROFINET name VIPA053 1PN00 xxx with xxx decimal value of position 2 8 3 21 2 4 22 4 5 23 8 6 24 16 7...
Страница 53: ...e stations are listed 6 Choose the PROFINET device with the suited MAC address and click on OK The MAC address may be found at the front of the module If the device name begins instead with vipa053 1pn00 so not all the switches of the address switch are 0 Please correct this 7 Enter at Assign device name the device name of your project and click at Assign Name The name is remanent stored in the PR...
Страница 54: ...le n Bit 1 Diagnostic interrupt 0 disable 1 enable n Bit 2 Diagnostic interrupt type 0 Vendor specific data 1 Channel specific data n Bit 3 Auto acknowledge 0 disable 1 enable n Bit 4 reserved n Bit 5 Web server 0 disable 1 enable n Bit 6 reserved n Bit 7 Data format 0 Data format Motorola 1 Data format Intel 0Fh 1 4 00h fix 00h 5 n Bit 0 FMM Activation 0 disable 1 enable n Bit 1 FMM automatic res...
Страница 55: ...terrupt is not acknowl edged by the PROFINET controller other interrupts of the module are blocked With Auto Acknowledge 1 each interrupt is automatically acknowledged by the PROFINET device In this mode the diagnostics data were always overwritten by new interrupts Default setting is Auto Acknowledge 1 For continuous use Auto Acknowledge should be activated n Data format Motorola Intel This param...
Страница 56: ... data by means of a DCP tool n Assign via an IO controller IP address data It gives you access to the Web server to accordingly change the IP address data there The web server is built dynamically and depends on the number of modules which are connected to the PROFINET IO device 1 Module list PROFINET IO device and System SLIO module in the plugged sequence 2 Functions for the module which is sele...
Страница 57: ...ess data of the PROFINET IO device n Firmware With this function you can bring in a firmware update You can get the appropriate firmware file from VIPA n Info Here product name order number serial number firmware version and hardware state number of the according module are listed n Data At Data the states of the inputs respectively outputs are listed n Parameter If available the parameter data of...
Страница 58: ... and is only supported by PROFINET IO device from VIPA n By default FMM is disabled To use the FMM mappings you have to activate FMM in the parametrization of the PROFINET IO device Ä Chap 4 4 1 Parameter data page 54 n For the FMM the mapping of the slots is to be specified via the record set 0x7F n For commissioning you have to activate the parameter Startup when expected actual configuration di...
Страница 59: ... configuration actual configu ration n 255 Virtual module module does not exist in the actual configuration Behaviour of a virtual module n The input area always has the value 0 regardless of its size n The writing to the output area has no effect n The following record sets can be read 0x8028 Read input data always 0 is read 0x8029 Read output data always 0 is read 0xAFF0 IM0 data a name determin...
Страница 60: ... MMI in a protected area 6 Create the configuration by defining the deviation of the actual and target configura tion for the current hardware configuration in record set 0x7F 7 Transfer this record set via write command to your IO device ð The configuration is stored permanently in the IO device and active with the next restart 4 6 3 Examples 4 6 3 1 Target configuration The FMM configuration alw...
Страница 61: ...ual 3 àFMM 3 n Slot 4 The module of Slottarget 4 is in the actual configuration at Slotactual 5 àFMM 5 n Slot 5 The module of Slottarget 5 is in the actual configuration at Slotactual 6 àFMM 6 n Slot 6 The module of Slottarget 6 is in the actual configuration at Slotactual 4 àFMM 4 Record set 0x7F Mapping 2 1 3 5 6 4 0 0 0 Slottarget The FMM configuration always refers to the slot of the target co...
Страница 62: ... module of Slottarget 5 is in the actual configuration at Slotactual 4 àFMM 4 n Slot 6 The module of Slottarget 6 is not available in the actual configuration à Mapping 255 Record set 0x7F Mapping 1 255 2 3 4 255 0 0 0 Slottarget The FMM configuration always refers to the slot of the target configuration Moduletarget Module at the slot of the target configuration Slotactual Slot of the actual conf...
Страница 63: ...lot 6 The module of Slottarget 6 is in the actual configuration at Slotactual 6 àFMM 6 Record set 0x7F Mapping 0 0 3 4 5 6 0 0 0 Slottarget The FMM configuration always refers to the slot of the target configuration Moduletarget Module at the slot of the target configuration Slotactual Slot of the actual configuration Moduleactual Module at the slot of the actual configuration FMM For variant 3 FM...
Страница 64: ...errupt VIPA specific 8002h ExtChannelDiag 1000h Hardware interrupt VIPA specific 28 47 VIPA specific Hardware interrupt data Hardware interrupt data see module description 4 7 2 Diagnostic interrupt n Diagnostics interrupt data of System SLIO modules with interrupt capability were automatically sent by a diagnostics message if the interrupt is activated by parametri zation at the corresponding mod...
Страница 65: ... PROFINET IO device 01F4h Error at System SLIO module n 8002h ExtChannelDiag refer to the table below 01FBh UserSpecifiedDiagnostics 01FBh 01F4h 7h Error at System SLIO module ChannelErrorType 7 Upper limit violation 28 47 VIPA specific Diagnostic interrupt data DS 1 Diagnostic record set 1 see module description 48 49 VIPA specific Slot Subslot 0101h Slot 1 Subslot 1 50 51 VIPA specific Channel n...
Страница 66: ...ing 32 33 ChannelErrorType see table 0007h Upper limit violation 34 35 VIPA specific ExtendedChannelErrorType n 0000h Error at PROFINET IO device n 01F4h Error at System SLIO module 01F4h Error at System SLIO module 36 39 VIPA specific ExtendedChannelAddValue n Diagnostic data DS 0 0000h 150Dh Diagnostic data record set 0 see module description ChannelErrorTypes Code Description 0001h Short circui...
Страница 67: ... Shared device error shared device is not supported by this hardware version 0109h FMM configuration was changed manual restart necessary 4 7 2 1 Acyclic access to the diagnostic data By means of the handling block SFB 52 RDREC the last sent diagnostics data can acyclically be read from the module 4 7 2 1 1 Diagnostic PROFINET IO device With Slot 0 Subslot 1 the PROFINET IO device is accessed Depe...
Страница 68: ...ersion n Bit 2 FMM configuration was changed manual restart necessary Ä Chap 4 6 Free Module Mapping FMM page 58 n Bit 7 3 00h fix 2 3 19 00h fix 4 7 2 1 2 Diagnostics data module With Slot 1 64 Subslot 1 the corresponding System SLIO module is accessed Depending on the Index you will get the following data n Index 0000h Record set DS 00h of the diagnostics data n Index 0001h Record set DS 01h of ...
Страница 69: ...t 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 n Bit 5 0 reserved n Bit 6 set at hardware interrupt lost n Bit 7 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Number of diagnostic bits per channel ERR_A Diagno...
Страница 70: ...te Bit 7 0 0 Information concerning the allocation may be found in the description of the corresponding System SLIO module Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CHxERR Channel specific ...
Страница 71: ... during configuration and stored in the module such as Installation location Installation data Via read record set special identification data may be accessed Here parts of the identifi cation data are addressed by the corresponding index number The record sets have the following structure Contents Length byte Coding hex Header n BlockType 2 I M0 0020h I M1 0021h I M2 0022h I M3 0023h n BlockLengt...
Страница 72: ...COUNTER read 2byte 0000h for internal usage IM_PROFILE_ID read 2byte 0000h for internal usage IM_PROFILE_SPECIFIC_TYPE read 2byte 0005h for internal usage IM_VERSION read 0101h Version of the I M data e g 0101h version 1 1 n IM_Version_Major 1byte n IM_Version_Minor 1byte IM_SUPPORTED read 2byte 000Eh I M1 I M3 are present Maintenance data 1 Index AFF1h IM_TAG_FUNCTION read write 32byte Unique dev...
Страница 73: ...M page 58 007Fh read DS 01h of the parameter data 0080h 0090h read DS 80h DS 90h of the parameter data 8000h 8001h 800Ah 800Bh 800Ch 8010h 8011h 8012h 8013h 801Eh 802Ah 802Bh 802Ch 802Dh 802Fh 8030h 8031h 8050h 8051h 8052h 8053h 8054h 8060h 8061h 8062h 8070h 8080h 8090h refer to the PROFINET specification 8028h read input data from a subslot 8029h read output data from a subslot AFF0h read I M 0 s...
Страница 74: ...ata 0080h 0090h write DS 80h DS 90h of the parameter data AFF1h write I M 1 identification and location AFF2h write I M 2 date of installation AFF3h write I M 3 comment AFF4h write I M 4 sign in module EEPROM Only PROFINET IO device Only System SLIO module VIPA System SLIO Deployment Index overview HB300 IM 053 1PN00 en 19 08 74 ...