510
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Code
Name
Causes
Possible Solutions
These parameters are set at the same time:
•
H1-xx = 62 [Speed Search from Fref]
•
H5-22 = 1 [Speed Search from MODBUS =
Enabled]
Remove one of the function settings.
Parameter
S3-01 ≠ 0 [PI2 Control Enable Selection ≠
Disabled]
and MFDI set for
H1-xx = AD [Select PI2
Control PI Parameters]
is ON or MFDI set for
H1-xx
= 1AD [!Select PI2 Control PI Parameters]
is OFF.
•
Set
S3-01 = 0
to use
H1-xx = AD or 1AD
for the adjustments of
S3-06 [PI2 Control Proportional Gain]
and
S3-07 [PI2 Control
Integral Time]
instead of the primary PI controller Proportional
and Integral adjustments.
•
When PI2 Control is necessary, remove the MFDI function
setting.
Code
Name
Causes
Possible Solutions
oPE05
Run Cmd/Freq Ref Source Sel Err
There is an option card installed on the drive.
Remove the option card from the drive. If it is compatible, install
the option card on the bypass control board.
The setting to assign the Run command or frequency
reference to an option card is incorrect.
Correct the parameter settings.
Z1-39 = 3 [Drive/Bypass Source Select = Option
PCB]
is set, but there is no option card connected.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB]
is set, but there is no option card
connected.
b1-02 = 3 [Run Command Selection 1 = Option
PCB]
is set, but there is no option card connected.
Connect an option card.
When
S5-04 = 0 [HAND-OFF-AUTO Behavior =
Legacy]
, you set
b1-02 ≠ 7, 8, or 9 [Run Command
Selection 1 ≠ AUTO C Term Run, AUTO
C Serial Run, or AUTO C
Option Run]
.
Set
b1-02 = 7, 8, or 9
.
When
S5-10 = 2 [AUTO Key Memory at Power
Down = AUTO Mode]
, you set
b1-02 = 0 [Keypad]
.
Change the
b1-02
or
S5-10
setting.
Code
Name
Causes
Possible Solutions
oPE07
Analog Input Selection Error
The settings for
H3-02 and H3-10 [MFAI Function
Selection]
and
H7-30 [Virtual Analog Input
Selection]
overlap.
Set
H3-02, H3-10, and H7-30
correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
•
Setting value
0 [Frequency Reference]
•
Setting values
F and 1F [Not Used]
Code
Name
Causes
Possible Solutions
oPE08
Parameter Selection Error
You set these parameters:
•
S1-01 = 1 [Dynamic Noise Control = Enabled]
•
Y4-42 ≠ 0 [Output Disconnect Detection Sel ≠
Disabled]
Set
S1-01 = 0
or
Y4-42 = 0
.
You set
L6-02 [Torque Detection Level 1]
<
L6-14
[Motor Underload Level @ Min Freq]
.
Set parameters to be
L6-02
≥
L6-14
.
Code
Name
Causes
Possible Solutions
oPE09
PID Control Selection Fault
These parameters are set at the same time:
•
b5-01 = 1
•
b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
And one of these parameters is set:
•
d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠
0.0%]
•
Y1-06 ≠ 0.0 [Minimum Speed ≠ 0.0%]
•
Y4-12 ≠ 0.0 [Thrust Frequency ≠ 0.0%]
•
YF-01≠ 0 [PI Aux Control Selection ≠ Disabled]
Correct the parameter settings.
Parameter
b5-01 = 3
and one of these parameters is
set at the same time:
•
d2-02 ≠ 0.0
•
Y1-06 ≠ 0.0
•
Y4-12 ≠ 0.0
•
YF-01≠ 0
Correct the parameter settings.
Note:
The drive detects this error if the PID control function selection is incorrect.
(When
b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim]
)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...