5.10 o: Keypad-Related Settings
372
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
Item
Number of
Characters
Description
1
Attribute
2
[02] shows that the record is a monitor data record.
2
File number
4
The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number in hexadecimal format.
3
Time stamp
12
Data log data was retrieved (YYMMDDHHMMSS)
4
Log Monitor Data 1
4
Monitor number selected by
o5-03 [Log Monitor Data 1]
5
Log Monitor Data 2
4
Monitor number selected by
o5-04 [Log Monitor Data 2]
:
:
:
:
13
Log Monitor Data 10
4
Monitor number selected by
o5-12 [Log Monitor Data 10]
14
Reserved
4
-
15
Encoding data
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
16
File number
6
Row number (Hex.) in the data log file
■
o5-01: Log Start/Stop Selection
No.
(Hex.)
Name
Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available on an HOA keypad.
0
(0 - 1)
Note:
You must insert a compatible SD cart into the keypad before you enable this parameter.
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in
o5-02 [Log Sampling Interval]
.
■
o5-02: Log Sampling Interval
No.
(Hex.)
Name
Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available on an HOA keypad.
100 ms
(100 - 60000 ms)
■
o5-03: Log Monitor Data 1
No.
(Hex.)
Name
Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available on an HOA keypad.
101
(000, 101 - 1299)
Note:
Set the
U monitor
number you want to log.
For example, to display
U1-01 [Frequency Reference]
, set
o5-03 = 101
. When it is not necessary to set a data log monitor, set this parameter
to
000
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...