SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
•
Output current is a minimum of 100% of the drive rated current and the frequency reference is less than 6 Hz.
•
Output current is a minimum of 109% of the drive rated current and the frequency reference is 7 Hz or more.
When the drive switches the carrier frequency to the set value, it uses a hysteresis of 12%.
3 : Enable at Overload
The drive decreases the carrier frequency at one of these conditions:
•
Output frequency is less than 6 Hz and output current is more than 120%
•
Output frequency is 7 Hz or more and the IGBT temperature detected by thermistor is high
■
L8-41: High Current Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
High Current Alarm
Selection
Sets the function to cause an
HCA [High Current Alarm]
when the output current is more than 150%
of the drive rated current.
0
(0, 1)
0 : Disabled
The drive will not detect an
HCA
.
1 : Enabled
If the output current is more than 150% of the drive rated current, the drive will detect an
HCA
.
The MFDO terminal set for an alarm
[H2-01 to H2-03 = 10]
activates.
■
L8-97: Carrier Freq Reduce during OH
No.
(Hex.)
Name
Description
Default
(Range)
L8-97
(3104)
Carrier Freq Reduce during
OH
Sets the function to decrease carrier frequency during oH pre-alarm.
0
(0, 1)
0 : Disabled
1 : Enabled
◆
L9: Drive Protection 2
L9 parameters
are used to configure the protection function used to detect cooling fan faults.
■
L9-16: FAn1 Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time
Sets the detection time for
FAn1 [Drive Cooling Fan Fault]
. Yaskawa recommends that you do not
change this parameter value.
4.0 s
(0.0 - 30.0 s)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...