F7-17: EtherNet/IP Speed Scaling Factor
No.
(Hex.)
Name
Description
Default
(Range)
F7-17
(03F5)
EtherNet/IP Speed Scaling
Factor
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-18: EtherNet/IP Current Scale Factor
No.
(Hex.)
Name
Description
Default
(Range)
F7-18
(03F6)
EtherNet/IP Current Scale
Factor
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-19: EtherNet/IP Torque Scale Factor
No.
(Hex.)
Name
Description
Default
(Range)
F7-19
(03F7)
EtherNet/IP Torque Scale
Factor
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-20: EtherNet/IP Power Scaling Factor
No.
(Hex.)
Name
Description
Default
(Range)
F7-20
(03F8)
EtherNet/IP Power Scaling
Factor
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-21: EtherNet/IP Voltage Scale Factor
No.
(Hex.)
Name
Description
Default
(Range)
F7-21
(03F9)
EtherNet/IP Voltage Scale
Factor
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-22: EtherNet/IP Time Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F7-22
(03FA)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
■
F7-23 to F7-32: Dynamic Out Param 1 to 10 for CommCard
No.
(Hex.)
Name
Description
Default
(Range)
F7-23 to F7-27
(03FB - 03FF)
F7-28 to F7-32
(0370 - 0374)
Dynamic Out Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set
F7-23
to
F7-27
to configurable Output 1-
5.
0
■
F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
(Hex.)
Name
Description
Default
(Range)
F7-33 to F7-42
(0375 - 037E)
Dynamic In Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set
F7-33
to
F7-37
to configurable inputs 1-5.
0
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...