1.13 o: Keypad-Related Settings
94
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o1-80
(31BA)
Fault Screen Display
Sets a full-screen display message to show on the keypad when a fault or CPF occurs.
0 : OFF
1 : ON
1
(0, 1)
o1-81
(31BB)
Alarm Screen Display
Sets a full-screen display message to show on the keypad when an alarm occurs.
0 : OFF
1 : ON
0
(0, 1)
o1-82
(31BC)
Message Screen Display
Sets a full-screen display message to show on the keypad when a status message is active.
0 : OFF
1 : ON
0
(0, 1)
◆
o2: Keypad Operation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o2-02
(0506)
OFF Key Function
Selection
Sets the function to use
on the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after you replace the control board.
Determined by the drive
(-)
o2-05
(0509)
Home Mode Freq Ref
Entry Mode
Sets the function that makes it necessary to push
to use the keypad to change the
frequency reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
0
(0, 1)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from
the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-09
(050D)
Reserved
-
-
o2-19
(061F)
Parameter Write during
Uv
Enables and disables the function to change parameter settings during a
Uv [DC Bus
Undervoltage]
condition. Use this parameter with 24 V Power Supply option revision B or
later.
Note:
If you enable this parameter and use a 24 V Power Supply option that is earlier than
revision B, the parameter changes can possibly not write correctly and it can cause a
CPF06 [EEPROM Memory Data Error]
fault.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disable
1 : Enabled
0
(0, 1)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...