TOEPYAIHV6002A HV600 Drive Programming
83
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L6-06
(04A6)
Torque Detection Time 2
Sets the detection time for Overtorque/Undertorque Detection 2.
0.1 s
(0.0 - 10.0 s)
L6-13
(062E)
Motor Underload Curve
Select
Sets the motor underload protection (
UL6 [Undertorque Detection 6]
) based on motor load
and sets the level of
L6-02 [Torque Detection Level 1]
to refer to Fbase or Fmax.
0 : Base Frequency Enable
1 : Max Frequency Enable
0
(0, 1)
L6-14
(062F)
Motor Underload Level
@ Min Freq
Sets the
UL6 [Undertorque Detection 6]
detection level at minimum frequency by
percentage of drive rated current.
15%
(0 - 300%)
◆
L7: Torque Limit
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L7-01
(04A7)
RUN
Forward Torque Limit
Sets the torque limit value for forward motoring as a percentage, where motor rated torque
is the 100% value.
200%
(0 - 300%)
L7-02
(04A8)
RUN
Reverse Torque Limit
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque
is the 100% value.
200%
(0 - 300%)
L7-03
(04A9)
RUN
Forward Regenerative
Trq Limit
Sets the torque limit value for forward regenerative conditions as a percentage of the motor
rated torque.
200%
(0 - 300%)
L7-04
(04AA)
RUN
Reverse Regenerative Trq
Limit
Sets the torque limit value for reversed regenerative conditions as a percentage of the
motor rated torque.
200%
(0 - 300%)
L7-16
(044D)
Torque Limit Process at
Start
Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
1
(0, 1)
◆
L8: Drive Protection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L8-02
(04AE)
Overheat Alarm Level
Sets the
oH
detection level temperature.
Determined by o2-04
(50 - 150 °C)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets drive operation if it detects an
oH
alarm.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
4
(0 - 4)
L8-05
(04B1)
Input Phase Loss
Protection Sel
Sets the function to enable and disable input phase loss detection.
0 : Disable
1 : Enabled
1
(0, 1)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output
phase loss detection when the output current decreases to less than 5% of the drive rated
current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
•
The motor rated current is very small compared to the drive rating.
•
The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1
(0 - 2)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...