E1-09:
Figure 2.60 Zero Speed Time Chart
ON : Output frequency <
E1-09
.
OFF : Output frequency
≥
E1-09
.
■
2: Speed Agree 1
Setting Value
Function
Description
2
Speed Agree 1
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-02 [Speed Agree Detection Width]
.
Note:
The detection function operates in the two motor rotation directions.
L4-02:
Figure 2.61 Speed Agree 1 Time Chart
ON : The output frequency is in the range of “frequency reference
±
L4-02
”.
OFF : The output frequency does not align with the frequency reference although the drive is
running.
■
3: User-Set Speed Agree 1
Setting Value
Function
Description
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02 [Speed Agree
Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection level.
ON : The output frequency is in the range of “
L4-01
±
L4-02
” and the range of frequency reference
±
L4-02
.
OFF : The output frequency is not in the range of “
L4-01
±
L4-02
” or the range of frequency
reference
±
L4-02
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...