3E: PID Setpoint Selection 1
Setting Value
Function
Description
3E
PID Setpoint Selection 1
Sets the function to switch the PID setpoint to
YA-02 [Setpoint 2]
or
YA-04 [Setpoint 4]
. Set this function and
H1-xx = 3F [PID
Setpoint Selection 2]
at the same time.
Note:
If you use this function and one of
H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-02
or
YA-04
is PID setpoint.
OFF : The frequency reference,
YA-01 [Setpoint 1]
, or
YA-03 [Setpoint 3]
is PID setpoint.
■
3F: PID Setpoint Selection 2
Setting Value
Function
Description
3F
PID Setpoint Selection 2
Sets the function to switch the PID setpoint to
YA-03 [Setpoint 3]
or
YA-04 [Setpoint 4]
. Set this function and
H1-xx = 3E [PID
Setpoint Selection 1]
at the same time.
Note:
If you use this function and one of
H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04]
at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-03
or
YA-04
is PID setpoint.
OFF : The frequency reference,
YA-01 [Setpoint 1]
, or
YA-02 [Setpoint 2]
is PID setpoint.
■
40: Forward RUN (2-Wire)
Setting Value
Function
Description
40
Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 41 [Reverse Run Command (2-Wire Seq)]
together.
ON : Forward Run
OFF : Run Stop
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm
EF [FWD/REV Run Command
Input Error]
and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)]
.
Figure 2.54 2-Wire Sequence Wiring Example
■
41: Reverse RUN (2-Wire)
Setting Value
Function
Description
41
Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 40 [Forward Run Command (2-Wire Seq)]
together.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...