When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2 (Stop
command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the drive operates
in the forward direction, and when it activates, the drive operates in the reverse direction.
WARNING!
Sudden Movement Hazard. Set the MFDI parameters before you close control circuit switches. Incorrect Run/Stop
circuit sequence settings can cause serious injury or death from moving equipment.
WARNING!
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you do
not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you
energize the drive.
Figure 2.47 3-Wire Sequence Wiring Example
.
Figure 2.48 3-Wire Sequence Time Chart
Note:
•
To input the Run command, activate the terminal for 1 ms minimum.
•
The default setting for
b1-17 [Run Command at Power Up]
is
0 [Disregard Existing RUN command]
. If you enable the Run command
when the drive is energized, the protective function activates and the
flashes quickly. When the application allows Run, set
b1-17 =
1 [Accept Existing RUN Command]
.
■
3: Multi-Step Speed Reference 1
Setting Value
Function
Description
3
Multi-Step Speed Reference
1
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
4: Multi-Step Speed Reference 2
Setting Value
Function
Description
4
Multi-Step Speed Reference
2
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...