TOEPYAIHV6002A HV600 Drive Programming
107
◆
S6: Protection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S6-01
(3236)
Emergency Override
Speed
Sets the speed command for emergency override mode when
S6-02 = 0 [Emergency
Override Ref Selection = Use S6-01 Reference]
.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
,
E1-09 [Minimum Output
Frequency]
(
E9-04 [Base Frequency]
) sets the lower limit, and
E1-04 [Maximum
Output Frequency]
(
E9-02 [Maximum Speed]
) sets the upper limit.
•
Parameter default is lower-limited to
E1-09
(
E9-04
when
A1-02 = 8
). The default
setting will automatically increase when
E1-09
(
E9-04
) >
S6-01
.
1.50 Hz
(1.50 - 60.00 Hz)
S6-02
(3237)
Emergency Override Ref
Selection
Sets the Emergency Override Speed Source:
0 : Use S6-01 Reference
1 : Use Frequency Reference
2 : System PID Mode
3 : Independent PID Mode
0
(0 - 3)
S6-03
(323A)
EMOVR Independent
PID Scale
Sets the scaling on the Emergency PID Feedback and Setpoint (if programmed) Analog
Inputs.
Note:
•
S6-05 [EMOVR Independent PID Unit Digit]
sets the resolution for this parameter.
•
S6-04 [EMOVR Independent PID Unit]
sets the units for this parameter.
100.00
(0.10 - 600.00)
S6-04
(323B)
EMOVR Independent
PID Unit
0 :
“
WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 :
“
Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
48
(0 - 50)
S6-05
(323C)
EMOVR Independent
PID Unit Digit
Sets the number of digits for
S6-06 [EMOVR PID Setpoint]
when
S6-02 = 3[Emergency
Override Ref Selection = Independent PID Mode]
.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
2
(0 - 3)
S6-06
(323D)
RUN
EMOVR PID Setpoint
Sets the PID Setpoint when
S6-02 = 3[Emergency Override Ref Selection = Independent
PID Mode]
.
Note:
When
S6-02 = 3
: units and resolution are dependent on
S6-04 [EMOVR Independent
PID Unit]
and
S6-05 [EMOVR Independent PID Unit Digit]
. Value is internally
limited to 300% of
S6-03 [EMOVR Independent PID Scale]
.
0.00
(0 - 600.00)
S6-07
(323E)
EMOVR Fault
Suppression Mode
Sets the drive to let Emergency Override disable faults during operation.
0 : Fault Suppression
1 : Test Mode
0
(0, 1)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...