TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
271
Table 8.2 BACnet Specifications
Item
Specifications
Interface
Master-Slave/Token-Passing (MS-TP)
RS-485
Communication parameter
Communications speed: 9.6, 19.2, 38.4, 76.8 kbps
Data length: 8 bit (fixed)
Parity: even, odd, none
Stop Bit: 1 bit (fixed)
Communication protocol
BACnet MS-TP
Number of possible units to connect
Maximum: 127 units for each MS-TP network segment depending on network conditions.
◆
Communication with the Controller
This section gives information about the settings for the termination resistor and how to connect to BACnet
communications.
■
Connect Communications Cable
Use this procedure to start communication between the controller and bypass.
1.
De-energize the bypass then connect the communications cable to the controller and the bypass. The bypass
uses terminal TB3 for serial communications.
Figure 8.2 Communications Cable Connection Terminal (TB3)
Note:
Isolate the communications wiring from the main circuit wiring and other high-power wiring. Use shielded wires for the
communications wiring and connect cable sheaths as shown in “Wiring Diagram for More than One Bypass”. Incorrect wiring
procedures could cause bypass malfunction because of electrical interference.
2.
Enable the termination resistor ONLY when the bypass is at the end of the communications network. Set DIP
switch S1 to the “ON” position to enable the termination resistor. Refer to “Set the Termination Resistor” for
more information.
3.
Energize the bypass.
4.
Use the keypad to set the necessary communications parameters
H5-01 to H5-12
.
•
H5-01 [Drive Node Address]
•
H5-02 [Communication Speed Selection]
•
H5-04 [Stopping Method after Com Error]
•
H5-05 [Comm Fault Detection Select]
•
H5-08 [Communication Protocol Selection]
•
H5-09 [CE Detection Time]
5.
Because communications parameters do not take effect immediately, either de-energize and re-energize the
bypass or set
H5-20 = 1 [Communication Parameters Reload = Reload Now]
.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...