4 Primary Operation Tests

YASKAWA

TOEPYAIH6R01 HV600 REDUNDANT DRIVE PRIMARY TEST OPERATION

11

Confirm Auto-Transfer Function

This test is optional based on the application requirements.

Table 4.4 Confirm Auto-Transfer Function

Check

Step

Details

Figure

16

Set the MAN-FAULT XFER-AUTO switch to

AUTO

.

17

Set the DRV A-AUTO-DRV B switch to

AUTO

.

18

Set the HAND-OFF-AUTO switch to

HAND

to start Drive A.

19

Confirm that you can use the BAS to change the speed reference for Drive A and Drive B.

-

20

If necessary, remove the front cover from Drive A to access the TB3 and TB4 terminal blocks below
the control board.

While Drive A is running, momentarily jumper terminal TB4 SN to TB3 S3 (external fault normally
open) to trigger a fault in Drive A.

Note:

When you jumper terminal SN to S3, Drive A will fault on an

EF3

fault code. Confirm that the

corresponding drive fault relay output is in a faulted state. Drive B will then attempt to start
immediately.

Confirm Drive B starts operating.

END

Содержание H6R B Series

Страница 1: ...P YA I H 6 R 0 1 M O D E L S H6RxBxxx Three Phase 480 V 3 to 250 HP A C D R I V E F O R H VA C F A N P U M P A P P L I C AT I O N S R E D U N D A N T D R I V E P R I M A R Y T E S T O P E R AT I O N H...

Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIH6R01 HV600 REDUNDANT DRIVE PRIMARY TEST OPERATION...

Страница 3: ...mental Safety Information 4 General Safety 4 2 Product Overview 5 How to Read Redundant Drive Catalog Codes 6 Models H6RxBxxx 7 3 Receiving and System Components 7 4 Primary Operation Tests 9 Primary...

Страница 4: ...al and the standard drive manuals General Safety General Precautions Some figures in the instructions include options and drives without covers or safety shields to more clearly show the inside of the...

Страница 5: ...ant Drive Package is engineered for use in critical HVAC building automation applications that require continuous reliable motor control This document provides a procedure to test the operation of the...

Страница 6: ...Use the information in Figure 2 1 and Table 2 2 to read the catalog codes Figure 2 1 Catalog Code Table 2 2 Catalog Code Details No Description 1 HV600 Redundant Drive 2 Enclosure type 1 IP20 UL Type...

Страница 7: ...2 250 1 Horsepower rating is based on standard NEMA B 4 pole motor design as represented in NEC table 430 150 Full Load Current Three Phase Alternating Current Motors at 480 volts 3 Receiving and Syst...

Страница 8: ...D SHIELD GND FE COMMUNICATIONS INPUT R COMMUNICATIONS INPUT R COMMUNICATIONS OUTPUT S COMMUNICATIONS OUTPUT S JUMPER SH1 to 122 SH1 from 124 RUNNING DRIVE ON POWER FAULT DRIVE AGREE 1 SPEED RUN FWD S1...

Страница 9: ...22 TB1 1SN 138 127 127 to 125 127 from 129 127 128 128 to 125 128 from 129 128 RUNNING DRIVE ON POWER FAULT DRIVE AGREE 1 SPEED RUN FWD S1 RUN REV S2 EXTERNAL FAULT N O S3 FAULT RESET S4 HAND MODE LO...

Страница 10: ...if necessary set min max speeds and accel decel times etc 11 When commissioning is complete set the HAND OFF AUTO switch to OFF to stop the drive Expanded Function Test Table 4 3 Expanded Function Tes...

Страница 11: ...t Drive A 19 Confirm that you can use the BAS to change the speed reference for Drive A and Drive B 20 If necessary remove the front cover from Drive A to access the TB3 and TB4 terminal blocks below...

Страница 12: ...12 YASKAWA TOEPYAIH6R01 HV600 REDUNDANT DRIVE PRIMARY TEST OPERATION Revision History Date of Publication Revision Number Revised Content August 2022 First release...

Страница 13: ...YASKAWA TOEPYAIH6R01 HV600 REDUNDANT DRIVE PRIMARY TEST OPERATION 13...

Страница 14: ...eu com www yaskawa eu com YASKAWA EL TRICO DO BRASIL LTDA 777 Avenida Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br In the event that the...

Отзывы: