488
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Code
Name
Causes
Possible Solutions
oFA38
Control Reference Error
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA39
Drive Receive Time Over 3
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA40
CtrlResSel 1Err
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA41
Drive Receive Time Over 4
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA42
CtrlResSel 2Err
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oFA43
Drive Receive Time Over 5
A fault occurred in the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oH
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature of the drive is more than the value set in
L8-02 [Overheat Alarm Level]
.
•
Measure the ambient temperature.
•
Increase the airflow in the control panel.
•
Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
•
Remove objects near the drive that are producing too much heat.
The load is too heavy.
•
Measure the output current.
•
Decrease the load.
•
Decrease the value set in
C6-02 [Carrier Frequency Selection]
.
The internal cooling fan of the drive stopped.
1.
Use the procedures in this manual to replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
.
Note:
•
The drive detects this fault if the heatsink temperature of the drive is more than the value set in
L8-02
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L8-03 [Overheat Pre-Alarm Selection]
.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...