406
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
T1-04: Motor Rated Current
No.
(Hex.)
Name
Description
Default
(Range)
T1-04
(0704)
Motor Rated Current
Sets the rated current (A) of the motor.
Determined by o2-04
(10% to 200% of the drive
rated current)
Set the motor rated current between 50% and 100% of the drive rated current for the best performance. Enter the
current at the motor base speed.
■
T1-05: Motor Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
T1-05
(0705)
Motor Base Frequency
Sets the base frequency (Hz) of the motor.
60.0 Hz
(0.0 - 400.0 Hz)
When you do Auto-Tuning, the drive sets
T1-05
to
E1-04 [Maximum Output Frequency]
. If
T1-05 < 40 Hz
,
E1-04
=
40 Hz. If you operate the drive at a speed that is higher than the base frequency, or if you operate in the field
weakening range, set
E1-04
to the maximum output frequency after you complete Auto-Tuning.
■
T1-06: Number of Motor Poles
No.
(Hex.)
Name
Description
Default
(Range)
T1-06
(0706)
Number of Motor Poles
Sets the number of motor poles.
4
(2 to 120)
■
T1-07: Motor Base Speed
No.
(Hex.)
Name
Description
Default
(Range)
T1-07
(0707)
Motor Base Speed
Sets the motor base speed for Auto-Tuning (min
-1
(r/min)).
1750 min
-1
(r/min)
(0 - 24000 min
-1
(r/min))
■
T1-11: Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
T1-11
(070B)
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
Determined by E2-11
(0 - 65535 W)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the
E2-10 [Motor Iron Loss]
for the motor output set in
T1-02 [Motor Rated Power]
. If the motor
test report is available, enter the motor iron loss value to
T1-11
.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...