12.11 o: Keypad-Related Settings
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
991
■
o4-23: Date Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LCD keypad.
2
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
Note:
The Fault History in the Monitor Mode shows when faults occurred. Refer to
Show Fault History on page 173
for more information.
■
o4-24: bAT Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-24
(310F)
RUN
bAT Detection Selection
Sets operation when the drive detects
bAT [Keypad Battery Low Voltage]
and
TiM [Keypad Time Not
Set]
.
0
(0 - 2)
0 : Disable
The drive will not detect
bAT
or
TiM
.
1 : Enable (Alarm Detected)
TiM
or
bAT
shows on the keypad, and operation continues. The output terminal set for Alarm
[H2-01
to
H2-03 = 10]
activates.
2 : Enable (Fault Detected)
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates, and MB-MC
deactivates.
◆
o5: Log Function
The data log function saves drive status information as a CSV file in the micro SD memory card in the keypad.
Monitors Ux-xx
are the source of data log information. You can record a maximum of 10 monitors.
Change the LCD keypad screen from the main menu to the Diagnostic Tools screen and select the data log function.
Set the number of the monitor to record and the sampling time, then start to record the data log.
Table 12.74 Setting Parameters for Data Log Items
No.
Name
Default
Data Log Monitors
o5-03
Log Monitor Data 1
101
U1-01 [Frequency Reference]
o5-04
Log Monitor Data 2
102
U1-02 [Output Frequency]
o5-05
Log Monitor Data 3
103
U1-03 [Output Current]
o5-06
Log Monitor Data 4
107
U1-07 [DC Bus Voltage]
o5-07
Log Monitor Data 5
108
U1-08 [Output Power]
o5-08
Log Monitor Data 6
000
Not selected
o5-09
Log Monitor Data 7
000
Not selected
o5-10
Log Monitor Data 8
000
Not selected
o5-11
Log Monitor Data 9
000
Not selected
o5-12
Log Monitor Data 10
000
Not selected
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...