Figure 3.39 External Dimensions of Crimp Ferrules
Table 3.13 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14
8
1.1
2.5
◆
Wiring the Control Circuit Terminal
WARNING!
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
NOTICE:
Do not let wire shields touch other signal lines or equipment. Insulate the wire shields with electrical tape or shrink tubing.
If you do not insulate the wire shields, it can cause a short circuit and damage the drive.
Note:
•
Isolate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2, +3) and other
high-power wiring. If control circuit wiring is adjacent to main circuit wiring, it can cause incorrect operation of the drive and equipment
from electrical interference.
•
Isolate wiring for contact output terminals MA, MB, MC and M1-M6 from other control circuit wiring. If contact output terminal wiring is
adjacent to other control circuit wiring, it can cause incorrect operation of the drive and equipment from electrical interference.
•
Use a Class 2 power supply to connect external power to the control terminals. If the power supply for peripheral devices is incorrect, it can
cause a decrease in drive performance.
•
Connect the shield of shielded cable to the applicable ground terminal. Incorrect equipment grounding can cause drive or equipment
malfunction from electrical interference.
Correctly ground the drive terminals and complete main circuit wiring before you wire the control circuit. Remove the
keypad and front cover.
1.
Push in on the tabs on the both sides of the LED status ring board to release the board from the bracket. Pull
the board forward to remove it.
NOTICE:
When you remove the LED Status Board from the drive bracket, make sure that you temporarily install it in the
holding position provided on the drive. If you cause damage to the LED status ring board, the LEDs will not function
correctly.
Note:
You can temporarily store the LED status ring board with the temporary placement holes on the drive. The location of the
temporary placement holes is different on different drive models.
A - Drive front
B - LED status ring board
C - Temporary placement holes
Figure 3.40 Remove the LED Status Ring Board
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...