n7-11: Pull-in Current Switch Hysteresis Band
No.
(Hex.)
Name
Description
Default
(Range)
n7-11
(311B)
Expert
Pull-in Current Switch
Hysteresis Band
Sets the hysteresis level for Switching Speed set in
n7-10 [Pull-in Current Switching Speed]
. When
the speed is lower than
n7-10
+
n7-11
during acceleration, the drive enables pull-in current.
5.0%
(1.0 - 20.0%)
Note:
•
The value set in
n8-51 [Pull-in Current @ Acceleration]
is enabled for speeds that are not higher than
n7-10
+
n7-11
during acceleration.
The value set in
b8-01 [Energy Saving Control Selection]
is enabled for speeds higher than
n7-10
+
n7-11
.
•
If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
•
When it is most important to save energy in the low speed range, decrease the setting value.
■
n7-13: Pull-in Current Switching Time
No.
(Hex.)
Name
Description
Default
(Range)
n7-13
(311D)
Expert
Pull-in Current Switching
Time
Sets a time to enable the pull-in current commands.
100 ms
(0 - 1000 ms)
If there is a large quantity of oscillation at speeds around
n7-10 [Pull-in Current Switching Speed]
, decrease the
setting in decrements of 20 ms.
■
n7-17: Resistance TemperatureCorrection
No.
(Hex.)
Name
Description
Default
(Range)
n7-17
(3122)
Resistance
TemperatureCorrection
Sets the function to adjust for changes in the motor resistance value caused by changes in the
temperature.
1
(0 to 2)
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Note:
•
For settings 1 and 2, the adjustment time can cause a delay before startup.
•
For settings 1 and 2, the drive can set the line-to-line resistance value of
E9-10 [Motor Line-to-Line Resistance]
.
•
When the temperature will change at startup, use setting 2.
•
To decrease the startup time, set this parameter to 0, then do line-to-line resistance tuning.
•
If you will start from coasting, set this parameter to 0, then do line-to-line resistance tuning.
◆
n8: PM Motor Control Tuning
n8 parameters
are used to make adjustments when controlling PM motors.
■
n8-01: Pole Position Detection Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-01
(0540)
Pole Position Detection
Current
Sets, as a percentage, the Initial Rotor Position Estimated Current, taking the
E5-03 [Motor Rated
Current (FLA)]
as the 100% value. Usually it is not necessary to change this setting.
50%
(0 - 100%)
The drive uses the Initial Rotor Position Estimated Current to detect the initial position of rotors.
Use the "Si" value on the motor nameplate, if available.
Note:
When
A1-02 = 7 [CLV/PM]
, this parameter takes effect only in Expert Mode.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...