YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
933
■
Mechanical Weakening Detection
The Mechanical Weakening Detection function detects the mechanical weakening of a machine that can cause
overtorque or undertorque because of motor speed and total drive operation time.
The drive activates the function if the drive total operation time is longer than the time set in
L6-11 [Mech Fatigue
Hold Off Time]
. You can use
U4-01 [Cumulative Ope Time]
to monitor the total operation time.
Parameter Settings
The drive detects Mechanical Weakening if overtorque or undertorque occur during the speed range set in
L6-08
[Mechanical Fatigue Detect Select]
and
L6-09 [Mech Fatigue Detect Speed Level]
for the length of time set in
L6-10
[Mech Fatigue Detect Delay Time]
. The drive uses
L6-01 to L6-03 [Torque Detection 1 Setting Parameter]
to detect
oL5 [Mechanical Weakening Detection 1]
or
UL5 [Mechanical Weakening Detection 2]
. Parameter
L6-08
sets the
operation after detection.
Set the terminal that outputs the fault in
H2-01 to H2-03 [MFDO Function Select]
.
Table 12.71 Mechanical Weakening Detection Settings Parameters
Configuration Parameter
Mechanical Deterioration Detection
MFDO Function Select
•
Terminals M1-M2
•
Terminals M3-M4
•
Terminals M5-M6
H2-01, H2-02, and H2-03 = 22
Operation Selection after Detection
L6-08
Detection Start Time
L6-11
Speed Range
Detection Criteria
L6-08
Detection Level
L6-09
Detection Time
L6-10
Overtorque
Detection Criteria
L6-01
Detection Level
L6-02
Detection Time
L6-03
■
L6-01: Torque Detection Selection 1
No.
(Hex.)
Name
Description
Default
(Range)
L6-01
(04A1)
Torque Detection Selection 1
Sets the speed range that detects overtorque and undertorque and the operation of drives (operation
status) after detection.
0
(0 - 8)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-02 [Torque
Detection Level 1]
for the length of time set in
L6-03 [Torque Detection Time 1]
. The drive detects undertorque if the
motor current or output torque is less than the level set in
L6-02
for the length the time set in
L6-03
.
0 : Disabled
The drive will not detect overtorque or undertorque.
1 : oL @ Speed Agree - Alarm only
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an
oL3 [Overtorque Detection 1]
and operation continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an
oL3
and operation
continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an
oL3 [Overtorque Detection 1]
and operation stops.
4 : oL @ RUN - Fault
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...