916
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
L2-11: KEB DC Bus Voltage Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
L2-11
(0461)
Expert
KEB DC Bus Voltage
Setpoint
Sets the target value that controls the DC bus voltage to a constant level in Single Drive KEB Ride-
Thru 2. Sets the DC bus voltage level that completes the KEB operation for all other KEB methods.
Determined by E1-01
(Determined by E1-01)
■
L2-29: Kinetic Energy Backup Method
No.
(Hex.)
Name
Description
Default
(Range)
L2-29
(0475)
Expert
Kinetic Energy Backup
Method
Sets the KEB function operation mode.
0
(0 - 3)
Set
L2-01 = 3, 4, or 5 [Momentary Power Loss Ope Select = KEB Mode, KEB Stop Mode, or KEB Decel to Stp]
or
KEB Ride-Thru 1/2 [H1-xx = 65, 66, 7A, or 7B]
, to enable the KEB function.
0 : Single Drive KEB Ride-Thru 1
The drive monitors the DC bus voltage and uses regenerative energy from the motor to hold the DC bus voltage at the
level set in
L2-11 [KEB DC Bus Voltage Setpoint]
.
The KEB operation continues and the deceleration rate changes as specified by
C1-09 [Fast Stop Time]
.
Note:
•
If the drive detects
Uv1 [DC Bus Undervoltage]
during KEB operation, decrease the value of
C1-09
.
•
If the drive detects
ov [Overvoltage]
during KEB operation, increase the value of
C1-09
.
1 : Single Drive KEB Ride-Thru 2
The drive does KEB operation and automatically calculates the deceleration rate to make sure that the main circuit
electrical energy and main current voltage from motor regenerative energy is equal to
L2-11 [DC Bus Vol Setpoint
during KEB]
.
2 : System KEB Ride-Thru 1
The drive does not monitor the DC bus voltage and decelerates as specified by the KEB deceleration time set in
L2-
06
.
Set
L2-06
to the time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. The drive can decelerate and keep constant deceleration rates for more than one drive.
Note:
If you keep constant deceleration rates for more than one drive, it can trigger
ov
faults. Use the dynamic braking option with System KEB
Ride-Thru 1 to prevent
ov
faults.
3 : System KEB Ride-Thru 2
The drive monitors the DC bus voltage and decelerates for the deceleration time set in
L2-06
.
If the DC bus voltage increases, the drive momentarily holds the frequency to prevent
ov
while deceleration
continues.
Note:
When you cannot use a dynamic braking option, use System KEB Ride-Thru.
■
L2-30: KEB Zero Speed Operation
No.
(Hex.)
Name
Description
Default
(Range)
L2-30
(045E)
Expert
KEB Zero Speed Operation
Sets the operation when the output frequency decreases below the zero level (DC braking injection
starting frequency) during KEB deceleration when
L2-01 = 3 to 5 [Power Loss Ride Through Select
= Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU Power, or Kinetic Energy Backup:
DecelStop]
.
0
(0, 1)
0 : Baseblock
1 : DC/SC Braking
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...