YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
893
Figure 12.114 Simple Closed Loop Speed Control Block Diagram
Enable Simple Closed Loop V/f Mode
1. Connect the encoder output pulse wiring to terminal RP.
2. Set
A1-02 = 0 [Control Method Selection = V/f Control]
.
3. Set
H6-01 = 3
.
4. Set
H6-02 [Terminal RP Frequency Scaling]
to the speed feedback (pulse train input signal) frequency at the time
when the frequency reference is 100%.
Make sure that
H6-04 [Terminal RP Function Bias]
= 0% and
H6-03 [Terminal RP Function Gain]
= 100%.
5. Select the detection method for the direction of motor rotation.
When you use an MFDI, set
H1-xx = 7E
.
6. Set
C5 parameters
related to ASR gain and integral time to adjust responsiveness.
Note:
•
Set
A1-02 = 0
and
H6-01 = 3
to show
C5 parameters
.
•
You cannot use Closed Loop V/f Control mode with the Motor Switch function.
■
H6-02: Terminal RP Frequency Scaling
No.
(Hex.)
Name
Description
Default
(Range)
H6-02
(042D)
RUN
Terminal RP Frequency
Scaling
Sets the frequency of the pulse train input signal used when the item selected with
H6-01 [Terminal
RP Pulse Train Function]
is input at 100%.
1440 Hz
(100 - 32000 Hz)
■
H6-03: Terminal RP Function Gain
No.
(Hex.)
Name
Description
Default
(Range)
H6-03
(042E)
RUN
Terminal RP Function Gain
Sets the gain used when the function in
H6-01 [Terminal RP Pulse Train Function]
is input to
terminal RP.
100.0%
(0.0 - 1000.0%)
■
H6-04: Terminal RP Function Bias
No.
(Hex.)
Name
Description
Default
(Range)
H6-04
(042F)
RUN
Terminal RP Function Bias
Sets the bias used when the function in
H6-01 [Terminal RP Pulse Train Function]
is input to
terminal RP. Sets a value at the time when the pulse train is 0 Hz.
0.0%
(-100.0 - 100.0%)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...