YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
885
Figure 12.111 Analog Output Gain/Bias Configuration Example 2
Calibrate Terminal FM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show
H4-02 [Terminal FM Analog Output Gain]
on the keypad.
Terminal FM outputs the analog signal when the monitor item that you set in
H4-01 [Terminal FM Analog Output
Select]
is 100%.
2. Adjust
H4-02
while referencing the meter scale connected to terminal FM.
3. Show
H4-03 [Terminal FM Analog Output Bias]
on the keypad.
Terminal FM outputs the analog signal when the monitor item that you set in
H4-01
is 0%.
4. Adjust
H4-03
while referencing the meter scale connected to terminal FM.
Calibrate Terminal AM
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show
H4-05 [Terminal AM Analog Output Gain]
on the keypad.
Terminal AM outputs the analog signal when the monitor item that you set in
H4-04 [Terminal AM Analog
Output Select]
is 100%.
2. Adjust
H4-05
while referencing the meter scale connected to terminal AM.
3. Show
H4-06 [Terminal AM Analog Output Bias]
on the keypad.
Terminal AM outputs the analog signal when the monitor item that you set in
H4-04
is 0%.
4. Adjust
H4-06
while referencing the meter scale connected to terminal AM.
■
H4-01: Terminal FM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-01
(041D)
Terminal FM Analog Output
Select
Sets the monitor number to send from MFAO terminal FM.
102
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal FM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-02: Terminal FM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-02
(041E)
RUN
Terminal FM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
100.0%
(-999.9 - +999.9%)
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
07 [Terminal FM Signal Level Select]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...