842
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
OFF : Speed control
Note:
When this function is enabled, set
d5-01 = 0 [Torque Control Selection = Speed Control]
.
Input the Speed/Torque Control Switchover Time
Use parameter
d5-06 [Speed/Torque Changeover Time]
to set the length of time, in milliseconds, that the drive will
wait to switch between speed and torque control. When the speed/torque control switchover signal changes in the time
set in
d5-06
, the three analog inputs will keep their present value. Complete the signal switchover with an external
source in this time.
Note:
Refer to
“
Switch Speed Control and Torque Control
”
for more information.
■
72: Zero Servo
Setting Value
Function
Description
72
Zero Servo
Sets the function to hold a stopped motor.
This function will hold a stopped motor if an external force is applied or an analog reference is offset.
Note:
•
Refer to
“
b9: Zero Servo
”
for more information.
•
When you use the Zero Servo function, keep the Run command ON. Zero servo stops the motor and if you turn OFF the Run command, it
will not have power.
■
75: Up 2 Command
Setting Value
Function
Description
75
Up 2 Command
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is activated. Set this
function and
H1-xx = 76 [Down 2 Command]
together.
When you activate the terminal set for Up2 Command, the bias will increase. When you activate the terminal set for
Down 2 Command, the bias will decrease. When you activate or deactivate the two commands, the drive will hold the
frequency reference.
gives information about the relation between operation of the Up/Down 2 Command
and
d4-01, d4-03, d4-05
.
Note:
•
When you use this function, use
d4-08
and
d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit]
to set the optimal bias limit value.
•
Refer to "d4: Frequency Ref Up/Down & Hold" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...