698
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
•
b5-59 [PID Setpoint3]
•
b5-60 [PID Setpoint4]
•
U5-01 [PID Feedback]
•
U5-04 [PID Setpoint]
•
U5-99 [PID Setpoint Command]
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
■
b5-40: Frequency Reference Monitor @PID
No.
(Hex.)
Name
Description
Default
(Range)
b5-40
(017F)
Frequency Reference
Monitor @PID
Sets the contents for monitor
U1-01 [Frequency Reference]
in PID control.
0
(0, 1)
0 : U1-01 Includes PID Output
Monitor
U1-01
shows the frequency reference that was increased or decreased by the PID output.
1 : U1-01 Excludes PID Output
Monitor
U1-01
shows the actual frequency reference.
■
b5-47: PID Trim Mode Output Reverse Sel
No.
(Hex.)
Name
Description
Default
(Range)
b5-47
(017D)
PID Trim Mode Output
Reverse Sel
Sets reverse motor rotation when the PID control output is negative.
1
(0, 1)
This parameter is enabled when
b5-01 = 3 or 4 [PID Mode Setting = Fref + PID Trim, Fref + PID Trim (D on
feedback)]
.
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse.
■
b5-53: PID Integrator Ramp Limit
No.
(Hex.)
Name
Description
Default
(Range)
b5-53
(0B8F)
RUN
PID Integrator Ramp Limit
Sets the responsiveness of PID control when the PID feedback changes quickly.
0.0 Hz
(0.0 - 10.0 Hz)
Note:
•
This parameter is disabled when set to 0.0 Hz.
•
When
b5-53 > 0.0 Hz
and the drive enables the integrator ramp limit, the PID integrator value limit is the range set by the output frequency
±
b5-53
.
•
When the PID feedback changes quickly, gradually decrease the this parameter in 0.1 Hz increments to decrease the speed of the response
of PID control.
■
b5-55: PID Feedback Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-55
(0BE1)
PID Feedback Monitor
Selection
Sets the monitor (
Ux-xx
) used as the PID Feedback. Set the
x-xx
part of the
Ux-xx [Monitor]
.
000
(000 - 999)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...