682
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
b3-26: Direction Determination Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-26
(01C7)
Expert
Direction Determination
Level
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
1000
(40 to 60000)
■
b3-27: Speed Search RUN/BB Priority
No.
(Hex.)
Name
Description
Default
(Range)
b3-27
(01C9)
Expert
Speed Search RUN/BB
Priority
Sets the conditions necessary to start Speed Search.
0
(0, 1)
Executes
Speed Search from Fmax or Fref [H1-xx = 61/62]
for initial speed searches or from the MFDI terminal.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
■
b3-29: Speed Search Back-EMF Threshold
No.
(Hex.)
Name
Description
Default
(Range)
b3-29
(077C)
Expert
Speed Search Back-EMF
Threshold
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search when
the motor induced voltage level is the same as the setting value. Usually it is not necessary to change
this setting.
10%
(0 - 10%)
To make adjustments, gradually decrease the setting value. If you decrease the setting value too much, speed search
will not operate correctly.
■
b3-31: Spd Search Current Reference Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-31
(0BC0)
Expert
Spd Search Current
Reference Lvl
Sets the current level that decreases the output current during Current Detection Speed Search.
1.50
(1.50 - 3.50)
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
■
b3-32: Spd Search Current Complete Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b3-32
(0BC1)
Expert
Spd Search Current
Complete Lvl
Sets the current level that completes Speed Search.
1.20
(0.00 - 1.49)
The Current Detection Speed Search gradually decreases the output frequency to search for the motor speed when the
output current is equal to or less than Speed Search Current Complete Level.
Set this parameter as a ratio of
E2-03 [Motor No-Load Current]
. The setting is a ratio with respect to 30% of the
motor rated current when
E2-03
≤
E2-01 [Motor Rated Current]
× 0.3.
Note:
The setting is a ratio with respect to
E9-06 [Motor Rated Current (FLA)]
× 0.5 when
A1-02 = 8 [Control Method Selection = EZOLV]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...