466
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
6.
Push
or
to select the backed-up parameter data, then push
.
The keypad will show the
“
End
”
message when the write process is complete.
Note:
The keypad display changes when the settings and conditions change.
A -
A1-02 [Control Method Selection]
settings
B -
o2-04 [Drive Model (KVA) Selection]
settings (2 or
3 digits)
C - Presence of DriveWorksEZ parameter backup
D - Parameter backup data is not registered
E - Backup data does not contain the date
Information
F - Backup date
◆
Verify Keypad Parameters and Drive Parameters
This procedure makes sure that the parameter setting values that you backed up in the keypad agree with the
parameter setting values in the drive.
Note:
•
Always stop the drive before you start to verify the parameters.
•
While you restore parameters, the drive will not accept Run commands.
1.
Push
(Home) to show the HOME screen.
Note:
• When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
• If the screen does not show [Home] for
, push
(Back), and then push
to show [Home].
2.
Push
(Menu).
3.
Push
or
to select [Parameter Backup/Restore], then push
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...