Code
Name
Causes
Possible Solutions
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
•
H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-63 ≠ F [Term M3-M4 Secondary Function ≠
Not Used]
•
H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-66 ≠ F [Term M5-M6 Secondary Function ≠
Not Used]
•
H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
It is not possible to set
H2-01 to H2-03 = 1xx [Inverse output of
xx]
when using output functions for logic operations (
H2-60,
H2-63, H2-66 ≠ F
).
These parameter pairs are set incorrectly:
•
H2-21 [Comparator 1 Lower Limit]
>
H2-22
[Comparator 1 Upper Limit]
•
H2-27 [Comparator 2 Lower Limit]
>
H2-28
[Comparator 2 Upper Limit]
•
Set parameters
H2-21
≤
H2-22
.
•
Set parameters
H2-27
≤
H2-28
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...